| Plan Review Notes For Permit 04021372 |
| Permit Number |
04021372 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-26 00:00:00 | DENIED: | | | 1.PLAN SHEET A-21 DETAIL 2, INDICATES | | | A 1HR FIRE RATED FLOOR/CEILING ASSEMBLY. | | | PLEASE PROVIDE UL LISTING FOR | | | PENETRATIONS THROUGH THE MEMBRANE AT | | | EACH GRILLE.PLEASE CLARIFY. | | | | | | 2.PLEASE NOTE, A SHAFT ENCLOSURE IS | | | NOT REQUIRED PER 2001 FBC 705.2.2, | | | FIRE DAMPER NOT REQUIRED. | | | | | | 3.PLAN SHEET M-1 UNIT C, O.A. APPEARS | | | TO BE LOCATED IN THE GARAGE.FRESH AIR | | | INTAKES SHALL BE LOCATED AS NOT TO | | | CIRCULATE CARBON MONOXIDE INTO HVAC | | | SYSTEM.PLEASE ADVISE. | | | | | | 4.PLAN SHEET M-2 UNIT 2L & 2R RETURN | | | AIR JUMPERS ARE NOT SIZED PROPERLY. | | | RETURN SHALL BE A MINIMUM OF 14".THE | | | TOTAL SUPPLY AIR INTO MASTER SUITE SHALL | | | BE USED WHEN SIZING THE RETURN FOR THE | | | MASTER SUITE.REVISED 2001 FBC(M) | | | 601.4 EXCEPTION #1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|