Plan Review Notes
Plan Review Notes For Permit 04021372
Permit Number 04021372
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-04-07 00:00:001) ALL SMOKE DETECTORS SHALL BE A
 MINIMUM OF THREE FEET FROM AC
 DIFFUSERS.
  
 2) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) THE REQUIRED FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 4) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 7) PLEASE EXPLAIN EXITING RATIONALE
 FROM INSIDE THE UNITS.
  
 8) EMERGENCY INSTRUCTIONS FOR
 RESIDENTS SHALL BE PROVIDED.
  
 9) WET FIRE HYDRANTS SHALL BE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 10) SUITABLE ROADS ARE REQUIRED DURING
 CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910