| Plan Review Notes For Permit 04021372 |
| Permit Number |
04021372 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-05 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LAUNDRY CIRCUIT CALCULATION MUST | | | COMPLY WITH 220.116(B).(1500 VA). | | | | | | 2} PLEASE LABLE THE ROOMS ON THE | | | ELECTRICAL PLANS TO CORRESPOND TO THE | | | ARCHITECTURAL PLANS. | | | | | | 3} PLEASE PROVIDE PLANS FOR ALL UNITS, | | | INCLUDING REVERSE UNITS. | | | | | | 4} THE PANEL SCHEDULE REFERS TO | | | "LIVING/BREAKFAST" ROOM.THE "BREAKFAST" | | | ROOM MUST COMPLY WITH 210.52, 20 AMP CIR | | | | | | 5} SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | | | | 6} NOTE THAT THE SIGNATURE OF THE EN- | | | GINEER IS REQUIRED ON HIS/HER SEAL PER | | | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE | | | STAMPS ARE NOT ACCEPTABLE PER F.B.P.E. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|