Plan Review Notes
Plan Review Notes For Permit 04021372
Permit Number 04021372
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.116(B).(1500 VA).
  
 2} PLEASE LABLE THE ROOMS ON THE
 ELECTRICAL PLANS TO CORRESPOND TO THE
 ARCHITECTURAL PLANS.
  
 3} PLEASE PROVIDE PLANS FOR ALL UNITS,
 INCLUDING REVERSE UNITS.
  
 4} THE PANEL SCHEDULE REFERS TO
 "LIVING/BREAKFAST" ROOM.THE "BREAKFAST"
 ROOM MUST COMPLY WITH 210.52, 20 AMP CIR
  
 5} SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 STAMPS ARE NOT ACCEPTABLE PER F.B.P.E.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026