| Plan Review Notes For Permit 04021371 |
| Permit Number |
04021371 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-16 00:00:00 | 1) PLEASE INDICATE WHAT FIRE HYDRANTS | | | WILL BE AVAILABLE WHEN THE BUILDING | | | IS UNDER CONSTRUCTION. | | | | | | 2) YOUR PERMIT RESPONSE FOR WALLS | | | AND CEILINGS ARE INCORRECT. CLASS A, | | | B, OR C IS THE RESPONSE REQUIRED NOT | | | PAINTED FINISH. | | | | | | 3) THE REQUIRED FIRE SPRINKLER SYSTEM | | | SHALL BE MONITORED BY A UL LISTED | | | COMPANY APPROVED FOR CENTRAL STATION | | | SERVICE. "STATION LOCATED AT GATEHOUSE | | | DOES NOT MEET THIS REQUIREMENT". | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|