| Plan Review Notes For Permit 04021371 |
| Permit Number |
04021371 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-14 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE GEC ON THE RISER DIAGRAM IS 1/0 | | | IT MUST BE 3/0 PER 250.66. | | | | | | 2} THE RISER DIAGRAM INDICATES A 50 AMP | | | RANGE RECER AND THE SCEDULE INDICATES A | | | 60 AMP FEEDER. PLEASE CORRELATE. | | | | | | 3} THE LOW VOLTAGE SYMBOLS IN THE LEGEND | | | DO NOT MATCH THE ONES USED ON THE | | | DRAWING. | | | | | | 4} UNIT 1424 NEEDS A RECEPTACLE IN THE | | | DINING ROOM ON THE 2ND FLOOR TO COMPLY | | | WITH 210.52(A)(1). | | | | | | 5} THERE IS NO DISCONNECT SHOWN FOR THE | | | CONDENSING UNIT FOR 1424. PLEASE SHOW | | | LOCATION. | | | | | | 6} A CERTIFICATE OF AUTHORIZATION NUMBER | | | IS REQUIRED ON THE TITLE BLOCK PER FAC | | | 61G15-23.002. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|