2004-03-25 00:00:00DENIED:
 1.PLEASE NOTE, DETAIL OF UL DESIGN
 L528 IN THE UL DIRECTORY DOES NOT
 INDICATE ANY PENETRATIONS THROUGH THIS
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR THE PENETRATIONS THROUGH THE RATED
 ASSEMBLY.
  
 2.PLEASE CLARIFY RATING ON PLAN SHEET
 A-10 DETAIL #4, THE 1HR RATING IS AT THE
 PARTITION WALL TO THE UNDERSIDE OF THE
 CEILING CORRECT?IF THIS IS CORRECT,
 THE FIRE DAMPER INDICATED ON PLAN SHEET
 M-1 IS NOT REQUIRED BECAUSE THE WALL
 DOES NOT CONTINUE ABOVE THE CEILING.
  
 3.CLARIFY O.A. DUCT, IT APPEARS TO BE
 ABOVE THE CEILING AND DOES NOT PENETRATE
 THE BOTTOM MEMBRANE OF THE ASSEMBLY OR
 AT THE POINT OF ENTRY, FIRE DAMPER IS
 NOT REQUIRED.
  
 4.PER 2001 FBC 705.2.2 EXCEPTION #1,
 A SHAFT ENCLOSURE IS NOT REQUIRED FOR
 OPENING TOTALLY WITHIN A DWELLING UNIT
 & CONNECTING FOUR STORIES OR LESS.
  
 5.PLANS SHALL BE SIGNED BY THE
 ENGINEER NOT STAMPED WITH THEIR
 SIGNATURE PER FS 471.025.
  