| Date |
Text |
| 2004-03-25 00:00:00 | DENIED: |
| | 1.PLEASE NOTE, DETAIL OF UL DESIGN |
| | L528 IN THE UL DIRECTORY DOES NOT |
| | INDICATE ANY PENETRATIONS THROUGH THIS |
| | ASSEMBLY.PLEASE PROVIDE UL LISTING |
| | FOR THE PENETRATIONS THROUGH THE RATED |
| | ASSEMBLY. |
| | |
| | 2.PLEASE CLARIFY RATING ON PLAN SHEET |
| | A-10 DETAIL #4, THE 1HR RATING IS AT THE |
| | PARTITION WALL TO THE UNDERSIDE OF THE |
| | CEILING CORRECT?IF THIS IS CORRECT, |
| | THE FIRE DAMPER INDICATED ON PLAN SHEET |
| | M-1 IS NOT REQUIRED BECAUSE THE WALL |
| | DOES NOT CONTINUE ABOVE THE CEILING. |
| | |
| | 3.CLARIFY O.A. DUCT, IT APPEARS TO BE |
| | ABOVE THE CEILING AND DOES NOT PENETRATE |
| | THE BOTTOM MEMBRANE OF THE ASSEMBLY OR |
| | AT THE POINT OF ENTRY, FIRE DAMPER IS |
| | NOT REQUIRED. |
| | |
| | 4.PER 2001 FBC 705.2.2 EXCEPTION #1, |
| | A SHAFT ENCLOSURE IS NOT REQUIRED FOR |
| | OPENING TOTALLY WITHIN A DWELLING UNIT |
| | & CONNECTING FOUR STORIES OR LESS. |
| | |
| | 5.PLANS SHALL BE SIGNED BY THE |
| | ENGINEER NOT STAMPED WITH THEIR |
| | SIGNATURE PER FS 471.025. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |
| | |
| | |
| | |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |