2004-04-07 00:00:00PLANS REVIEW PERFORMED ON 3/4/03
  
 1) ALL SMOKE DETECTORS ARE TO BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS.
  
 2) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 3) THE REQUIRED FIRE SPRINKLER
 SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 4) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS. IF THE FRONT DOORS
 DO NOT FRONT A STREET, ADDRESSES WILL
 BE REQUIRED ON BOTH SIDES FOR FIRE
 AND PARAMEDICAL AND POLICE.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) PLEASE INDICATE INTERIOR FINISH
 FOR WALLS AND CEILINGS.
  
 7) PLEASE EXPLAIN EXITING RATIONALE
 FROM INSIDE THE UNITS.
  
 8) EMERGENCY INSTRUCTIONS FOR
 RESIDENTS SHALL BE PROVIDED.
  
 9) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 10) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION.
  
 11) PLEASE INDICATE IF GARAGE DOOR
 IS RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL