| Plan Review Notes For Permit 04021371 |
| Permit Number |
04021371 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-07 00:00:00 | PLANS REVIEW PERFORMED ON 3/4/03 | | | | | | 1) ALL SMOKE DETECTORS ARE TO BE | | | INSTALLED A MINIMUM OF THREE FEET | | | FROM AC DIFFUSERS. | | | | | | 2) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | | | | 3) THE REQUIRED FIRE SPRINKLER | | | SYSTEM SHALL BE MONITORED BY A UL | | | LISTED CENTRAL STATION APPROVED FOR | | | CENTRAL STATION SERVICE. | | | | | | 4) BUILDING ADDRESSES NOT SHOWN ON | | | ELEVATION DRAWINGS. IF THE FRONT DOORS | | | DO NOT FRONT A STREET, ADDRESSES WILL | | | BE REQUIRED ON BOTH SIDES FOR FIRE | | | AND PARAMEDICAL AND POLICE. | | | | | | 5) ALL NEW STAIRS SHALL HAVE HANDRAILS | | | ON BOTH SIDES. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | FOR WALLS AND CEILINGS. | | | | | | 7) PLEASE EXPLAIN EXITING RATIONALE | | | FROM INSIDE THE UNITS. | | | | | | 8) EMERGENCY INSTRUCTIONS FOR | | | RESIDENTS SHALL BE PROVIDED. | | | | | | 9) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 10) SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION. | | | | | | 11) PLEASE INDICATE IF GARAGE DOOR | | | IS RATED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|