| Notes |
| Date |
Text |
| 2004-03-29 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE ELECTRICAL PLANS FOR | | | ALL UNIT TYPES, INCLUDING REVERSE | | | TYPE'S. | | | | | | 2} PLEASE PUT ROOM LABELS ON ELECTRICAL | | | PLANS.(DEN,BEDROOM, ETC.) | | | | | | 3} THE LAUNDRY CALCULATION MUST BE | | | 1500 VA PER 220.16(B). | | | | | | 4} THE 1VA PER OUTLET CALCULATION IS | | | ONLY USED FOR BANKS AND OFFICE | | | BUILDINGS, IT IS NOT NECESSARY AND | | | CANNOT BE USED FOR DWELLINGS PER | | | 220.3(B). | | | | | | 5} PLEASE INCLUDE THE HEATING OR AIR | | | CONDITIONING LOAD IN THE CALCULATION | | | PER 220.30(C). | | | | | | 6} THE PANEL SCHEDULE INDICATES A | | | BREAKFAST ROOM. PLEASE SEE 210.52(C) | | | FOR WIRE AND OCP SIZE.(#12/20 AMP.) | | | | | | 7} THE RISER DIAGRAM INDICATES A 50 AMP | | | OUTLET FOR THE RANGE, THE PANEL SCHEDULE | | | INDICATES A 60 AMP BREAKER. PLEASE | | | CORRELATE. | | | | | | 8} UNIT 1424 2ND FLOOR NEEDS A | | | RECEPTACLE ADDED TO COMPLY WITH | | | 210.52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|