 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE ELECTRICAL PLANS FOR
 ALL UNIT TYPES, INCLUDING REVERSE
 TYPE'S.
  
 2} PLEASE PUT ROOM LABELS ON ELECTRICAL
 PLANS.(DEN,BEDROOM, ETC.)
  
 3} THE LAUNDRY CALCULATION MUST BE
 1500 VA PER 220.16(B).
  
 4} THE 1VA PER OUTLET CALCULATION IS
 ONLY USED FOR BANKS AND OFFICE
 BUILDINGS, IT IS NOT NECESSARY AND
 CANNOT BE USED FOR DWELLINGS PER
 220.3(B).
  
 5} PLEASE INCLUDE THE HEATING OR AIR
 CONDITIONING LOAD IN THE CALCULATION
 PER 220.30(C).
  
 6} THE PANEL SCHEDULE INDICATES A
 BREAKFAST ROOM. PLEASE SEE 210.52(C)
 FOR WIRE AND OCP SIZE.(#12/20 AMP.)
  
 7} THE RISER DIAGRAM INDICATES A 50 AMP
 OUTLET FOR THE RANGE, THE PANEL SCHEDULE
 INDICATES A 60 AMP BREAKER. PLEASE
 CORRELATE.
  
 8} UNIT 1424 2ND FLOOR NEEDS A
 RECEPTACLE ADDED TO COMPLY WITH
 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  