| Plan Review Notes For Permit 04021368 |
| Permit Number |
04021368 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-03-24 00:00:00 | FEEDERS REVISED TO SHOW SE CABLE, | | | HOWEVER PLANS/RISER STILLS SHOWS BEING | | | INSTALLED IN CONDUIT. CALLED ELECTRICAL | | | ENGINEER,CONDUIT IS NOT BEING USED. THIS | | | IS A MISPRINT ON PLANS. | | | CONDUIT CROSSED OUT ON PLANS PER | | | ENGINEER'S REQUEST. | | | | | | | | | WASHER VA REDLINED, SHOULD BE 1500VA | | | 220.16 | | | | | | IF PLANS ARE REVISED FOR ANY FUTURE | | | ITEMS, PLEASE ADJUST THE ABOVE AT THAT | | | TIME. |
|