| 2004-07-29 00:00:00 | NOTE: BEFORE THE CERTIFICATE OF |
| | OCCUPANCY IS ISSUED THE RECORDED |
| | DECLARATION OF CONDOMINIUM WILL BE |
| | REQUIRED. |
| | |
| | 1) ENERGY CALCS. ARE REQUIRED FOR EACH |
| | UNIT TYPE AND LOCATION (EXTERIOR AND |
| | INTERIOR). THE CONDITIONED SPACE ON THE |
| | FORMS DIFFERS FROM THE ONES LISTED ON |
| | THE PLANS. PLEASE CORRECT. |
| | |
| | 2) MASTERED PLANS ARE NOT ALLOWED TO BE |
| | REDLINED. SEE SHEETS A10, S7 AND S5. |
| | PLEASE CORRECT SEPIAS. |
| | |
| | 3) DETAIL 4 ON S1 IS INCORRECT. IT |
| | SHOULD BE A SECTION OF THE EXTERIOR WALL |
| | AND FOOTING. |
| | |
| | 4) THE FOUNDATION NOTES #3,4,& 5 ON S1 |
| | REFER TO SHEETS S3 AND S4 FOR DETAILS. |
| | HOWEVER, THERE ARE NO FOUNDATION NOTES |
| | ON S3 OR S4. PLEASE CORRECT. |
| | |
| | 5) ON SHEET A12, DETAIL #2 IS MISSING |
| | THE FIRESTOP BETWEEN THE VERTICAL AND |
| | HORIZONTAL AREAS. WALL SHEATHING SHOULD |
| | EXTEND TO BOTTOM OF FLOOR TRUSSES. |
| | PLEASE CORRECT. |
| | |
| | 6) FIRESTOP IS ALSO MISSING AT CONCEALED |
| | SPACES WHERE HORIZONTAL AND VERTICAL |
| | SPACES INTERSECT AT SECTIONS 11 AND 13 |
| | ON S7. SEE FBC 2305.1.4. |
| | |
| | 7) SHEET S2 HAS AN ID MARK FOR A DETAIL |
| | #17 ON S7. THERE IS NO SUCH DETAIL. |
| | PLEASE CORRECT. |
| | |
| | 8) THE PRODUCT APPROVAL SUBMITTED FOR |
| | THE FRONT DOOR INDICATES THAT THE DOOR |
| | IS NOT RATED FOR IMPACT AND IS REQUIRED |
| | TO BE SHUTTERED. PLANS SPECIFY THIS DOOR |
| | IS REQUIRED FOR EGRESS AND IS NOT TO BE |
| | SHUTTERED. PLEASE CORRECT. |
| | |
| | 9) REVISE THE UPLIFT VALUE LISTED IN THE |
| | SCHEDULE ON S4 FOR THE SIMPSON HETAL 20. |
| | THE MAXIMUM UPLIFT VALUE IS 1810# IN THE |
| | 2004 SIMPSON CATALOG, WHICH DOES NOT |
| | INCLUDE A ONE-THIRD INCREASE IN THE |
| | STEEL CALCULATIONS. |
| | |
| | 10) REVIEW THE TRUSS DRAWINGS AND REVISE |
| | THE CONNECTORS SPECIFIED FOR TRUSSES |
| | THAT EXCEED THE UPLIFT VALUES GIVEN IN |
| | SCHEDULE FOR THE SPECIFIED CONNECTOR. |
| | MARK (F) AN H10 IS NOT ADEQUATE FOR |
| | TRUSSES T4B, T4, T3, T2, T1, H2, AND H1. |
| | MARK (H) AN H3 AND MARK (A) A HETAL 12 |
| | ARE ALSO INADEQUATE FOR SOME OF THE |
| | TRUSS UPLIFTS FOR WHICH THEY ARE |
| | SPECIFIED. PLEASE CORRECT. |
| | |