2004-04-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE EQUIPMENT GND CONDUCTOR
 SIZE ON THE RISER DIAGRAM PER 250.122.
  
 2} THE DRAWING SHOWS A MAIN DISCONNECT
 AND 8 "METERS AND DISCONNECTS". THE
 RISER INDICATES A 6GANG METER CENTER
 WITH NO MAIN. PLEASE CORRELATE.
  
 3} THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.16.(1500 VA).
  
 4} PLEASE LABEL ROOMS ON THE ELECTRIC
 PLANS TO CORRESPOND WITH THE
 ARCHITECTURAL PLANS.
  
 5} PLEASE PROVIDE PLANS FOR ALL UNITS,
 INCLUDING REVERSED MODELS.
  
 6} NOTE THAT THE "NOOK" 7 DINING ROOM
 MUST COMPLY WITH 210.52(B).
  
 7} THE DINING ROOMIN UNIT "2203" MUST
 HAVE 2 RECEPTACLES ADDED TO COMPLY WITH
 210.52(A).
  
 8} THE PANEL SCHEDULE REFERS TO
 "LIVING/BREAKFAST" ROOM, THE BREAKFAST
 ROOM
 MUST BE ON A 20 AMP CIRCUIT TO COMPLY
 WITH 210.52(B), HOWEVER THERE IS NO
 ROOM LABLED LIKE THAT ON THE
 ARCHITECTURAL PLANS.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODESTAMPED SIGNATURES ARE NOT
 ACCEPTABLE.
  