| 2004-04-01 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE THE EQUIPMENT GND CONDUCTOR |
| | SIZE ON THE RISER DIAGRAM PER 250.122. |
| | |
| | 2} THE DRAWING SHOWS A MAIN DISCONNECT |
| | AND 8 "METERS AND DISCONNECTS". THE |
| | RISER INDICATES A 6GANG METER CENTER |
| | WITH NO MAIN. PLEASE CORRELATE. |
| | |
| | 3} THE LAUNDRY CIRCUIT CALCULATION MUST |
| | COMPLY WITH 220.16.(1500 VA). |
| | |
| | 4} PLEASE LABEL ROOMS ON THE ELECTRIC |
| | PLANS TO CORRESPOND WITH THE |
| | ARCHITECTURAL PLANS. |
| | |
| | 5} PLEASE PROVIDE PLANS FOR ALL UNITS, |
| | INCLUDING REVERSED MODELS. |
| | |
| | 6} NOTE THAT THE "NOOK" 7 DINING ROOM |
| | MUST COMPLY WITH 210.52(B). |
| | |
| | 7} THE DINING ROOMIN UNIT "2203" MUST |
| | HAVE 2 RECEPTACLES ADDED TO COMPLY WITH |
| | 210.52(A). |
| | |
| | 8} THE PANEL SCHEDULE REFERS TO |
| | "LIVING/BREAKFAST" ROOM, THE BREAKFAST |
| | ROOM |
| | MUST BE ON A 20 AMP CIRCUIT TO COMPLY |
| | WITH 210.52(B), HOWEVER THERE IS NO |
| | ROOM LABLED LIKE THAT ON THE |
| | ARCHITECTURAL PLANS. |
| | |
| | 9} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 10} NOTE THAT THE SIGNATURE OF THE EN- |
| | GINEER IS REQUIRED ON HIS/HER SEAL PER |
| | 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODESTAMPED SIGNATURES ARE NOT |
| | ACCEPTABLE. |
| | |