2004-03-29 00:00:00DENIED:
 1.PLANS SHALL BE SIGNED WITH ENGINEERS
 ORIGINAL SIGNATURE AND NOT STAMPED PER
 FS 471.025.
  
 2.FIRE DAMPERS INDICATED ON PLAN SHEET
 M-1 UNIT A, RATING APPEARS TO BE AT THE
 WALL AND CEILING, THE WALL DOES NOT
 CONTINUE ABOVE THE CEILING.FIRE DAMPER
 NOT REQUIRED.
  
 3.PLAN SHEET A-21 INDICATES THE
 FLOOR/CEILING AS A 1HR FIRE RATED
 ASSEMBLY.UL LISTING FOR L528 DOES NOT
 INDICATE PENETRATIONS THROUGH RATED
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR PENETRATIONS (DUCT).INDICATE IF
 RADIATION CEILING DAMPERS ARE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.