Plan Review Notes
Plan Review Notes For Permit 04021358
Permit Number 04021358
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-29 00:00:00DENIED:
 1.PLAN SHEET A-21 DETAIL 2, INDICATES
 A 1HR FIRE RATED FLOOR/CEILING ASSEMBLY.
 PLEASE PROVIDE UL LISTING FOR
 PENETRATIONS THROUGH THE MEMBRANE AT
 EACH GRILLE.PLEASE CLARIFY.
  
 2.PLEASE NOTE, A SHAFT ENCLOSURE IS
 NOT REQUIRED PER 2001 FBC 705.2.2,
 FIRE DAMPER NOT REQUIRED.
  
 3.PLAN SHEET M-1 UNIT C, O.A. APPEARS
 TO BE LOCATED IN THE GARAGE.FRESH AIR
 INTAKES SHALL BE LOCATED AS NOT TO
 CIRCULATE CARBON MONOXIDE INTO THE HVAC
 SYSTEM.
  
 4.PLAN SHEET M-2 UNIT 2L & 2R RETURN
 AIR JUMPER NOT SIZED PROPERLY(MASTR BRM)
 RETURN SHALL BE MINIMUM OF 14".THE
 TOTAL SUPPLY AIR INTO MASTER SUITE SHALL
 BE USED WHEN SIZING THE RETURN FOR THE
 MASTER SUITE.REVISED 2001 FBC(M)
 601.4 EXCEPTION #1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.