Plan Review Notes
Plan Review Notes For Permit 04021355
Permit Number 04021355
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER SHOWS A MAIN DISCONNECT,
 THE DRAWING SHOWS METERS AND
 DICONNECTS. PLEASE CORRELATE.
  
 2} INDICATE THE SIZE OF THE EQ. GND WITH
 THE FEEDERS ON THE RISER.
  
 3} THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.116(B).(1500 VA).
  
 4} PLEASE LABEL THE ROOMS ON THE ELECTR
 ICAL PLANS TO CORRESPOND TO THE ARCHITEC
 TURAL PLANS.
  
 5} THE PANEL SCHEDULE REFERS TO "LIVING/
 BREAKFAST" ROOM.THE "BREAKFAST" ROOM
 MUST COMPLY WITH 210.52(B),20 AMP CIRC.
  
 6} PLEASE NOTE SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 7} THE CALCULATION FOR "OUTLETS 1X.....)
 IS ONLY USED FOR OFFICE BUILDINGS AND
 BANKS. SEE "B"NOTE AT BOTTOM OF TABLE.
  
 10} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 STAMPS ARE NOT ACCEPTABLE PER F.B.P.E.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026