Plan Review Notes
Plan Review Notes For Permit 04021353
Permit Number 04021353
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-29 00:00:00DENIED:
 1.PLANS SHALL BE SIGNED WITH ENGINEERS
 ORIGINAL SIGNATURE AND NOT STAMPED PER
 FS 471.025.
  
 2.FIRE DAMPERS INDICATED ON PLAN SHEET
 M-1 UNIT A, RATING APPEARS TO BE AT THE
 WALL AND CEILING, THE WALL DOES NOT
 CONTINUE ABOVE THE CEILING.FIRE DAMPER
 NOT REQUIRED.
  
 3.PLAN SHEET A-21 INDICATES THE
 FLOOR/CEILING AS A 1HR FIRE RATED
 ASSEMBLY.UL LISTING FOR L528 DOES NOT
 INDICATE PENETRATIONS (DUCT) THROUGH
 RATED ASSEMBLY.PLEASE PROVIDE UL
 LISTING FOR PENETRATIONS (DUCT).
 INDICATE IF RADIATION CEILING DAMPER
 ARE REQUIRED.
  