Plan Review Notes
Plan Review Notes For Permit 04021350
Permit Number 04021350
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-29 00:00:00DENIED:
 1.PLAN SHEET A-21 DETAIL2, INDICATES
 A 1HR FIRE RATED FLOOR/CEILING ASSEMBLY.
 PLEASE PROVIDE UL LISTING FOR
 PENETRATIONS THROUGH THE MEMBRANE AT
 EACH GRILLE.PLEASE CLARIFY.
  
 2.PLEASE NOTE, A SHAFT ENCLOSURE IS
 NOT REQUIRED PER 2001 FBC 705.2.2,
 FIRE DAMPER NOT REQUIRED.
  
 3.PLAN SHEET M-1 UNIT C, O.A. APPEARS
 TO BE LOCATED IN THE GARAGE.FRESH AIR
 INTAKES SHALL BE LOCATED AS NOT TO
 CIRCULATE CARBON MONOXIDE INTO HVAC
 SYSTEM.PLEASE ADVISE.
  
 4.PLAN SHEET M-2 UNIT 2L & 2R RETURN
 AIR JUMPERS ARE NOT SIZED PROPERLY.
 RETURN SHALL BE A MINIMUM OF 14".THE
 TOTAL SUPPLY AIR INTO MASTER SUITE SHALL
 BE USED WHEN SIZING THE RETURN FOR THE
 MASTER SUITE.REVISED 2001 FBC(M)
 601.4 EXCEPTION #1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.