| Date |
Text |
| 2004-06-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FHA-98 AMEND. DESIGN MANUAL |
| | |
| | 1) PER FHA DESIGN MANUAL REQUIREMENT 7B |
| | SPECIFICATION "A" OR "B" TO BE INDICATED |
| | FOR EACH UNIT TYPE. |
| | 2) SHOW HEIGHT OF LAVS PER FHA DESIGN |
| | MANUAL PAGE 7.52. (34" MAX). |
| | 3) SHOW DETAIL FOR BACKING AT SIDE WALL |
| | OF WATER CLOSET PER PAGE 6.4 OF THE FHA |
| | DESIGN MANUAL. |
| | 4) SHT AP A5.04 ROOF PLAN KEY NOTES 4 & |
| | 5 ARE NOT SHOWN. PLEASE CLARIFY. SECTION |
| | 104.2.1- SHTS AP A5.12, A5.25, A5.32, |
| | AND A5.42 ALSO. |
| | 5) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW SQUARE FOOT- |
| | AGE FOR EACH AREA. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED |
| | TO SF OF ROOF. SHOW AREAS OF ROOF DRAIN- |
| | ING ONTO ROOF FROM ABOVE. SECTIONS 1106 |
| | AND 1107 AND ALL SUBSECTIONS. |
| | 6) SUBMIT A DETAIL FOR SECONDARY ROOF |
| | DRAINS. SECTION 1O4.2.1. |
| | 7) SHOW LOCATIONS FOR ALL SECONDARY ROOF |
| | DRAINS. SECTION 104.2.1. |
| | 8) SHT AP A5.70 SUBMIT DETAILS FOR SECT- |
| | IONS 11-4.15, 11-4.16, 11-4.19, 11-4.22 |
| | AND ALL SUBSECTIONS. |
| | 9) SHT AP A5.71 SUBMIT A DETAIL FOR THE |
| | SMOOTHIE BAR & THEATER/CONF. ROOM SINKS |
| | PER 11-4.24 AND ALL SUBSECTIONS. |
| | 10) SUBMIT A DETAIL FOR THE TRASH CHUTE |
| | WASH DOWN. SHOW WATER SUPPLY SIZE AND |
| | SHOW REQUIRED BACKFLOW. SECTION 104.2.1 |
| | 11) SHTS P14.02 UNITS B3 & B4 AND RISER |
| | S/5. MAXIMUM 4 FIXTURE UNITS ALLOWED ON |
| | 2" WET VENT. TABLE 909.3 (MASTER BATH) |
| | 12) SHT P14.04 2ND FLOOR CLUBHOUSE PLUMB |
| | ING PLAN. KITCHEN SINK SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT FOR THE TOIL- |
| | ET ROOM. - ALSO SEE SANT. RISER S/9. |
| | 13) SUBMIT A SANITARY BLDG DRAIN ISOMET- |
| | RIC RISER DIAGRAM. SHOW PIPE SIZE, AND |
| | DFU'S AS THEY ACCUMULATE IN THE SYSTEM. |
| | INDICATE TOTAL FIXTURE UNITS FOR EACH |
| | SANITARY RISER. SECTION 104.3.1.1 |
| | 14) AN RPZ BACKFLOW IS REQURED AT EACH |
| | BUILDING. SECTION 608.13.2 |
| | 15) SHT AP 14.27 THERMAL EXPANSION CON- |
| | TROL IS REQUIRED PER SECTION 607.3.2 |
| | SUBMIT DETAIL. |
| | 16) SHT AP 14.27 WATER HEATER DETAIL, |
| | DIELECTRIC UNIONS ARE NOT APPROVED FOR |
| | USE IN THE WATER SYSTEM. DELETE FROM DE- |
| | TAIL. |
| | 17) SUBMIT WATER RISER DIAGRAMS. SHOW |
| | PIPE SIZE. SECTION 104.3.1.1 - SHOW |
| | WATER HAMMER ARRESTORS REQUIRED BY SECT- |
| | ION 604.9 AND LOCATED PER PDI-WH 201. |
| | 18) SUBMIT A BLDG STORM DRAIN ISOMETRIC |
| | AND STORM RISER DIAGRAMS. SHOW PIPE SIZE |
| | AND INDICATE SQUARE FOOTAGE AS I ACCUMU- |
| | LATES IN THE BLDG STORM DRAIN. SECTION |
| | 104.3.1.1 |
| | 19) SUBMIT A CONDENSATE RISER DIAGRAM. |
| | SHOW ALL PIPE SIZES. SECTION 104.3.1.1. |
| | 20) SUBMIT BLDG DRAIN ISOMETRIC FOR THE |
| | PAN DRAIN LINES. MINIMUM DRAIN LINE UN- |
| | DERGROUND IS 2". SECTION 710.3 |
| | 21) APPLICATIONS ARE FOR BLDGS 1, 2, & 3 |
| | BUT PLANS SHOW BLDGS. 4 & 5. PLEASE |
| | CLARIFY. SECTION 104.2.1 |
| | 22) PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 - PER FBPE'S RULING INITIALS |
| | ARE NOT ACCEPTABLE. MINIMUM OF FIRST AND |
| | LAST REQUIRED FOR SIGNATURE ON SEALED |
| | PLANS. |
| | 23) FLOOR DRAINS SHOWN ON BLDG DRAIN |
| | SYSTEM ARE NOT APPROVED FOR THE SANITARY |
| | SYSTEM. THESE ARE AREA DRAINS FOR THE |
| | PARKING GARAGE AND SHALL CONNECT TO THE |
| | STORM SYSTEM. |
| | 24) PLANS DO NOT SEEM TO BE COMPLETE AND |
| | ADDITIONAL COMMENTS MAY BE ADDED NEXT |
| | REVIEW IF MORE INFORMATION IS AVAILABLE. |
| | |
| | REVIEW BY KEN STEVENS |