Plan Review Notes
Plan Review Notes For Permit 04021300
Permit Number 04021300
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 AMEND. DESIGN MANUAL
  
 1) PER FHA DESIGN MANUAL REQUIREMENT 7B
 SPECIFICATION "A" OR "B" TO BE INDICATED
 FOR EACH UNIT TYPE.
 2) SHOW HEIGHT OF LAVS PER FHA DESIGN
 MANUAL PAGE 7.52. (34" MAX).
 3) SHOW DETAIL FOR BACKING AT SIDE WALL
 OF WATER CLOSET PER PAGE 6.4 OF THE FHA
 DESIGN MANUAL.
 4) SHT AP A5.04 ROOF PLAN KEY NOTES 4 &
 5 ARE NOT SHOWN. PLEASE CLARIFY. SECTION
 104.2.1- SHTS AP A5.12, A5.25, A5.32,
 AND A5.42 ALSO.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW SQUARE FOOT-
 AGE FOR EACH AREA. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO SF OF ROOF. SHOW AREAS OF ROOF DRAIN-
 ING ONTO ROOF FROM ABOVE. SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS.
 6) SUBMIT A DETAIL FOR SECONDARY ROOF
 DRAINS. SECTION 1O4.2.1.
 7) SHOW LOCATIONS FOR ALL SECONDARY ROOF
 DRAINS. SECTION 104.2.1.
 8) SHT AP A5.70 SUBMIT DETAILS FOR SECT-
 IONS 11-4.15, 11-4.16, 11-4.19, 11-4.22
 AND ALL SUBSECTIONS.
 9) SHT AP A5.71 SUBMIT A DETAIL FOR THE
 SMOOTHIE BAR & THEATER/CONF. ROOM SINKS
 PER 11-4.24 AND ALL SUBSECTIONS.
 10) SUBMIT A DETAIL FOR THE TRASH CHUTE
 WASH DOWN. SHOW WATER SUPPLY SIZE AND
 SHOW REQUIRED BACKFLOW. SECTION 104.2.1
 11) SHTS P14.02 UNITS B3 & B4 AND RISER
 S/5. MAXIMUM 4 FIXTURE UNITS ALLOWED ON
 2" WET VENT. TABLE 909.3 (MASTER BATH)
 12) SHT P14.04 2ND FLOOR CLUBHOUSE PLUMB
 ING PLAN. KITCHEN SINK SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT FOR THE TOIL-
 ET ROOM. - ALSO SEE SANT. RISER S/9.
 13) SUBMIT A SANITARY BLDG DRAIN ISOMET-
 RIC RISER DIAGRAM. SHOW PIPE SIZE, AND
 DFU'S AS THEY ACCUMULATE IN THE SYSTEM.
 INDICATE TOTAL FIXTURE UNITS FOR EACH
 SANITARY RISER. SECTION 104.3.1.1
 14) AN RPZ BACKFLOW IS REQURED AT EACH
 BUILDING. SECTION 608.13.2
 15) SHT AP 14.27 THERMAL EXPANSION CON-
 TROL IS REQUIRED PER SECTION 607.3.2
 SUBMIT DETAIL.
 16) SHT AP 14.27 WATER HEATER DETAIL,
 DIELECTRIC UNIONS ARE NOT APPROVED FOR
 USE IN THE WATER SYSTEM. DELETE FROM DE-
 TAIL.
 17) SUBMIT WATER RISER DIAGRAMS. SHOW
 PIPE SIZE. SECTION 104.3.1.1 - SHOW
 WATER HAMMER ARRESTORS REQUIRED BY SECT-
 ION 604.9 AND LOCATED PER PDI-WH 201.
 18) SUBMIT A BLDG STORM DRAIN ISOMETRIC
 AND STORM RISER DIAGRAMS. SHOW PIPE SIZE
 AND INDICATE SQUARE FOOTAGE AS I ACCUMU-
 LATES IN THE BLDG STORM DRAIN. SECTION
 104.3.1.1
 19) SUBMIT A CONDENSATE RISER DIAGRAM.
 SHOW ALL PIPE SIZES. SECTION 104.3.1.1.
 20) SUBMIT BLDG DRAIN ISOMETRIC FOR THE
 PAN DRAIN LINES. MINIMUM DRAIN LINE UN-
 DERGROUND IS 2". SECTION 710.3
 21) APPLICATIONS ARE FOR BLDGS 1, 2, & 3
 BUT PLANS SHOW BLDGS. 4 & 5. PLEASE
 CLARIFY. SECTION 104.2.1
 22) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - PER FBPE'S RULING INITIALS
 ARE NOT ACCEPTABLE. MINIMUM OF FIRST AND
 LAST REQUIRED FOR SIGNATURE ON SEALED
 PLANS.
 23) FLOOR DRAINS SHOWN ON BLDG DRAIN
 SYSTEM ARE NOT APPROVED FOR THE SANITARY
 SYSTEM. THESE ARE AREA DRAINS FOR THE
 PARKING GARAGE AND SHALL CONNECT TO THE
 STORM SYSTEM.
 24) PLANS DO NOT SEEM TO BE COMPLETE AND
 ADDITIONAL COMMENTS MAY BE ADDED NEXT
 REVIEW IF MORE INFORMATION IS AVAILABLE.
  
 REVIEW BY KEN STEVENS