| Date |
Text |
| 2004-05-10 00:00:00 | DENIED: |
| | PLEASE NOTES, PLANS APPEAR TO BE |
| | INCOMPLETE. |
| | |
| | 1.PERMIT APPLICATION INDICATES A 4 |
| | STORY OVER PARKING GARAGE. PLEASE SUBMIT |
| | PLANS ON VENTILATION FOR THE GARAGE. |
| | INDICATE OPEN OR CLOSED GARAGE.PROVIDE |
| | CALCULATIONS PER 2001 FBC 411.3.2 OR |
| | 411.4.2. |
| | |
| | 2.PLAN SHEETS M15.01 THROUGH M15.03, |
| | RETURN AIR TRANSFER FROM MASTER |
| | BEDROOMS SHALL BE SIZED PER THE REVISED |
| | 2001 FBC(M) 601.4 EXCEPTION #2 &3; 50 SQ |
| | INCHES OF CLEAR SPACE PER 100 CFM OF |
| | SUPPLY AIR.ALL SUPPLY AIR INTO THE |
| | MASTER SUITE IS TO BE INCLUDED FOR THE |
| | "TOTAL" AIR INTO THAT SPACE. |
| | |
| | 3.PLAN SHEET M15.12 DETAIL FOR THE |
| | RETURN AIR TRANSFER.SHOW COMPLIANCE |
| | WITH 2001 FBC(M) 603.8 & CHAPTER 13 SUB |
| | SUB-CHAPTER 610.1.ABC.3.6 OF THE FBC. |
| | |
| | 4.PLEASE PROVIDE A FLOOR PLAN FOR THE |
| | CORRIDORS.INDICATE VENTILATION & |
| | EQUIPMENT THAT WILL SERVE THE COMMON |
| | AREA. |
| | |
| | 5.INDICATE WHERE THE TRASH & FIRE PUMP |
| | ROOM ARE LOCATED (GARAGE, ROOF, ETC.). |
| | |
| | 6.PLAN SHEET M15.12 AHU MOUNTING |
| | DETAIL #3, INDICATES DUCT SUPPORTED ON |
| | THE BOTTOM CHORD.PROVIDE |
| | DOCUMENTATION THAT THE BOTTOM CHORD IS |
| | DESIGNED TO SUPPORT EQUIPMENT FROM THE |
| | BOTTOM OF THE TRUSS. |
| | |
| | 7.PLAN SHEET M15.12 AHU MOUNTING |
| | DETAIL, PER 2001 FBC(M) 603.1.3, A |
| | MINIMUM OF 4" CLEARANCE AROUND THE AHU |
| | SHALL BE PROVIDED. |
| | |
| | 8.AUXILIARY DRAIN PAN WITH OVERFLOW |
| | PROTECTION REQUIRED PER 2001 FBC |
| | 307.2.3. |
| | |
| | 9.CONDENSING UNIT STANDS LOCATED ON |
| | THE ROOF SHALL COMPLY WITH 2001 FBC |
| | 1511.7 FOR HEIGHT REQUIREMENT BETWEEN |
| | THE FINISHED ROOF & THE BOTTOM OF THE |
| | SUPPORT RAIL. |
| | |
| | 10. PROVIDE OUTSIDE AIR CALUCALTIONS FOR |
| | THE RESIDENCE AS WELL AS COMMON AREAS |
| | PER 2001 FBC(M) 403.3.SHOULD 402.2 BE |
| | USED, PROVIDE RESULTS FROM TESTING |
| | AGENCY SHOWING THE ACTUAL FILTRATION |
| | RATE FOR EACH WINDOW AND DOOR.PLEASE |
| | INDICATE CALCULATION ON THE PLAN |
| | SHOWINGCOMPLIANCE WITH 2001 FBC(M) |
| | 402.2. |
| | |
| | 11.PROVIDE INFORMATION FOR THE |
| | CONDENSATE. |
| | |
| | 12.PLEASE NOTE DRYER EXHAUST DUCT |
| | SHALL NOT EXCEED 25' WITH A 5' REDUCTION |
| | FOR EACH 90 DEGREE EL & 2 1/2' FOR EACH |
| | 45 DEGREE EL.2001 FBC(M) 504.6 |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |