2004-05-05 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) STAIRS ARE REQUIRED TO BE KEPT UP
 WITH CONSTRUCTION.
  
 3) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED WHEN THE BUILDING REACH
 THREE STORIES OR THIRTY FEET IN HEIGHT.
  
 4) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 5) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 6) THE PHASING PLAN NOTES ARE NOT
 CORRECT. ALL LIFE SAFETY EQUIPMENT AND
 DEVICES MUST BE INSPECTED, TESTED AND
 APPROVED PRIOR TO ANY OCCUPANCY
 BEING PERMITTED IN THE BUILDING. NO
 ELECTRICAL POWER WILL BE GRANTED
 UNTIL THE FIRE SPRINKLER SYSTEM AND
 THE FIRE ALARM SYSTEMS ARE READY.
 THE CITY HAS A POLICY WITH REGARDS TO
 RELEASE OF POWER. PLEASE REVIEW
 POLICY.
  
 7) ELEVATORS MUST BE PRESENT TO BE
 UTILIZED BY RESIDENTS.
  
 8) KNOX-BOXES WILL BE REQUIRED ON
 THE OUTSIDE OF THE BUILDINGS.
  
 9) KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED ON ALL FIRE DEPARTMENT
 CONNECTIONS.
  
 10) PLEASE CLEARLY IDENTIFY ALL
 EXIT STAIRS THAT LEAD DIRECTLY TO
 THE EXTERIOR. ALL EXIT STAIRS CANNOT
 TERMINATE WITHIN THE BUILDING.(S)
  
 11) IF THE BUILDINGS ARE GOING TO
 BE CONSIDERED SEPARATE, THEN ALL FIRE
 SPRINKLER, FIRE ALARM, AND MECHANICAL,
 ELECTRICAL, AND PLUMBING SYSTEMS SHALL
 BE SEPARATE.
  
 12) STAIR # 10 APPEAR TO BE OPEN.
 PLEASE EXPLAIN RATIONALE.
  
 13) TRAVEL DISTANCE NOTES IS INCORRECT.
 THE MAXIMUM TRAVEL DISTANCE IN A
 SPRINKLERED BUILDING FROM AN APARTMENT
 TO AN EXIT SHALL NOT EXCEED 200 FEET.
 OTHER AREAS OF THE BUILDING CAN BE
 MEET 250 FEET. PLEASE ADVISE OR
 REVISE.
  
 14) EXIT SIGN PLACEMENT CANNOT EXCEED
 100 FEET.
  
 15) THERE ARE STAIRS THAT ARE NOT
 SEPARATED.
  
 16) ON PAGE A2.01 IT SAYS "THE LOFTS
 AT CITY PLACE PROPOSED DEVELOPMENT".
 CLEARLY THIS INFORMATION IS NOT
 CORRECT. ALSO AN ELEVATION APPEARS
 IMPOSED ON THE DRAWING.
  
 17) SITE PLAN DOES NOT DISPAY ANY
 FIRE HYDRANT LOCATIONS.
  
 18) DOORS 1.005 AND 1.006 ON PAGE
 AP A5.01 OPPOSE ONE ANOTHER.
  
 19) DOORS MISSING FROM STAIRWAYS.
  
 20) THE FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 21) THE FIRE PROTECTION SITE PLAN
 DISPLAYS A FIRE MAIN WITH NO
 TERMINATION POINT OR CONNECTION
 POINT.
  
 22) THERE APPEARS THAT MORE DOORS
 ON THE DOOR SCHEDULE SHOULD BE FIRE
 RATED.
  
 23) ELEVATORS WARNING SIGNS ARE
 REQUIRED.
  
 24) BUILDING ADDRESSES REQUIRED ON
 PROPER ELEVATIONS.
  
 25) CLUBHOUSE DOORS 208 AND 203
 WHEN OPENED TOGETHER WILL BLOCK
 THE HALLWAY.
  
 26) PLEASE EXPLAIN WHERE CLUBHOUSE
 DOOR 201 TERMINATES TO.
  
 27) A TWO HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN PARKING AREAS AND
 OTHER AREAS OF THE BUILDING.
  
 28) ELECTRONIC SWITCHES WILL BE
 REQUIRED ON THE FIRE LINE BACKFLOW
 DEVICES.
  
 29) ANOTHER FIRE HYDRANT APPEARS
 TO BE NEEDED NEAR THE ENTRANCE TO THE
 SITE.
  
 30) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT.
  
 31) PLANS NEED TO BE BETTER ORGANIZED.
 THEY APPEAR VERY CONFUSING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL