| 2004-05-04 00:00:00 | *** IN FOR REVIEW *** |
| | SEE NOTES TO FOLLOW. |
| | PLANS SUBMITTED 2/26 |
| | ************ UNSAT **************** |
| | |
| | 1)NOTE: PLEASE PROVIDE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH WITH THE |
| | SUBMITTED PANEL SCHEDULES FOR UNITS. |
| | PLEASE SHOW ALL MIN CIRCUITS PER 2002 |
| | NEC. UNABLE TO VERIFY AT THIS TIME. |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING EM LTS. CLUBHOUSE? |
| | |
| | 3)NOTE: PLEASE SEE BLDG ONE. |
| | MAINS TO BE GROUPED, 230.72 |
| | |
| | 4)NOTE: PLEASE SEE OTHER BLDGS, SOME |
| | SHOW ELECTRICAL ROOMS, OTHERS DO NOT. |
| | |
| | 5)NOTE: PLEASE SHOW ALL CIRCUITING FOR |
| | BLDG/HOUSE POWER. PLANS ALSO NOT |
| | COMPLETED FOR REVIEW OF CODE COMPLIANCE. |
| | |
| | 6)NOTE: PLEASE CORRELATE OCP FOR APT |
| | UNIT FEEDERS. ALL SHOWN AT 125A'S YET |
| | SOME FEEDERS ARE ONLY RATED FOR 100A'S? |
| | |
| | 7)NOTE: PLEASE SEE RISER, NOTHING IS |
| | SHOWN FOR FIRE PUMP WHICH IS SHOWN FOR |
| | BLDG ONE??? PLEASE SEE 695.4B1 |
| | 230.72,230.70,230.76,230.79 ETC |
| | PLEASE SUBMIT SPECS FOR FIRE PUMP, |
| | FIRE PUMP CONTROLLER. WILL THERE BE A |
| | GENERATOR? |
| | |
| | 8)NOTE: PLEASE SEE 250.50 FOR ALL REQ'D |
| | ATTACHMENTS FOR GE SYSTEM. |
| | FOOTER STEEL. |
| | |
| | 9)NOTE: PLEASE SEE ONLY 3 PERMITS WERE |
| | APPLIED FOR AND PLANS SHOWS 5 BLDGS AND |
| | CLUBHOUSE?? |
| | |
| | 10)NOTE: PLEASE SEE NOTE ON E16.26, |
| | MENTIONS ARC FAULT PROETCTION FOR |
| | BEDROOM RECEPTS. PLEASE SEE 2002 NEC |
| | THIS IS REQ'D FOR ALL OUTLETS, INCLUDING |
| | LTS/ SD'S. |
| | |
| | 11)NOTE: PLEASE VERIFY IF SD'S WILL BE |
| | INSTALLED INSIDE SLEEPING ROOMS OR DOES |
| | BLDGS MEET THE EXCEPTIONS SET FORTH IN |
| | NFPA-72, LS 101 |
| | |
| | ***PLEASE SUBMIT COMPLETED PLANS FOR |
| | REVIEW FOR CODE COMPLIANCE TO 2002 NEC. |
| | THERE MAY BE OTHER COMMETS DUE TO PLANS |
| | NOT BEING COMPLETE AT THIS TIME. |
| | |