Plan Review Notes
Plan Review Notes For Permit 04021300
Permit Number 04021300
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021300
 ADD: N. CONGRESSBLDG# 1
 CONT:CONTEUVEST CONST
 TEL: (407)509-9707
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 PLANS ARE INCOMPLETE TO DO A THROUGH
 REVIEW. THE PLANS DO NOT INDICATE THE
 4 HR FIREWALL SEPERATING BUILDINGS
 LARGER THAN ALLOWED BY TABLE 500. THIS
 PLAN ALSO IS OVER THE ALLOWABLE HEIGHT
 IN TABLE 500. THE PHASING OF THE BUILD-
 ING # 1 IS MISSING STAIRWELLS FOR 1/3RD
 THE DIAGONAL. PLANS ARE MISSING ENCLOSUR
 ES ON VARIOUS STAIRWELLS. STRUCTURAL
 PLANS DO NOT GIVE STRUCTURAL DIMENSIONS.
  
  
 FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026