| 2004-02-27 00:00:00 | PROVISO: | | | 1.TERMINATION OF EXHAUST SHALL BE A | | | MINIMUM OF 10 FT FROM PROPERTY LINES, | | | ADJACENT OR CONTINGUOUS BUILDING AS WELL | | | AS FRESH AIR INTAKES. | | | | | | 2.PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE FIRE WRAP ON THE | | | JOBESITE AT THE TIME OF INSPECTION. | | | PLEASE NOTE, DUCT NOT TO BE COVERED | | | PRIOR TO THE INSPECTION OF WELDS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|