Plan Review Notes
Plan Review Notes For Permit 04021265
Permit Number 04021265
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT D-1 ALL DEMO'D AND ABANDONED PIPE
 SHALL BE INSPECTED PRIOR TO COVERING.
 2) DEAD ENDS SHALL BE PROHIBITED WHEN
 REMOVING ANY PART OF A DRAINAGE SYSTEM.
 SECTION 704.5
 3) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) FIRST FLOOR KITCHEN SINKS SHALL NOT
 CONNECT TO THE WET VENTED HORIZONTAL
 BRANCH DRAIN FOR THE POWDER ROOM. FIX-
 TURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. SECTION 909.1.
 B) SECOND FLOOR WASH MACHINE SHALL NOT
 CONNECT TO THE WET VENTED HORIZONTAL
 BRANCH DRAIN FOR THE MASTER BATHROOM.
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. SECTION 909.1.
 C) A FIXTURE SHALL NOT BE DOUBLE TRAPP-
 ED. WATER CLOSETS HAVE AN INTEGRAL TRAP
 AND DO NOT REQUIRE A TRAP ON THE RISER
 DIAGRAM. SECTION 1002.1
 D) WASH MACHINE REQUIRES A STANDPIPE &
 A CLEANOUT 4' ABOVE THE FLOOR PER SECT-
 IONS 1002.1, 802.4, AND 708.10.
 4) THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT. SEPARATE GAS PERMIT IS
 REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED).
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SECTION
 304. - FOR BOTH THE WATER HEATER ROOM
 AND THE DRYER ROOM.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 5) SEAL FOR ARCHITECT SHALL MAKE AN IM-
 PRESSION ON THE SURFACE OF THE PRINTS OR
 DRAWINGS. NO INFORMATION IS SHOWN ON THE
 SEALED PLANS. FAC 61G1-16.001
 6) LICENSE AA0003566 SHOWS ARCHITECT
 BUSINESS NUMBER FOR TEKTONICA DESIGN INC
 NOT BORGLUND TYSON, LLC AS SHOWN ON THE
 TITLE BLOCK. FIRM NAME SHALL BE ON TITLE
 BLOCK PER 61G1-16.004(1).
 7) A CERTIFICATE OF AUTHORIZATION IS RE-
 QUIRED PER FS 481.219(2) & (3). SHOW THE
 CERTIFICATE OF AUTHORIZATION ON TITLE
 BLOCK OF EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]