2004-04-05 00:00:00DENIED:
 1.PLAN SHEET M-1, PLEASE CLARIFY
 RETURN AIR DUCT TERMINATING INTO THE
 STORAGE ROOM.IS THIS DUCT TIED INTO
 THE AHU?
  
 2.PLEASE INDICATE IF THE WATER HEATER
 IS GAS OR ELECTRIC.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PLAN SHEET M-2 RETURN AIR DUCT TO
 THE MASTER BEDROOM DOES NOT INDICATE
 DUCT SIZE.PLEASE NOTE WHEN SIZING THE
 RETURN AIR FOR THE MASTER BEDROOM, ALL
 SUPPLY AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED IN THE CALCULATION FOR A
 "TOTAL" OF SUPPLY AIR TO THE SUITE.
 REVISED 2001 FBC(M) 601.4 EXCEPTION #3.
 PLEASE SIZE RETURN AIR TO THE MASTER
 SUITE ACCORDINGLY.
  