Plan Review Notes
Plan Review Notes For Permit 04021243
Permit Number 04021243
Review Stop E
Sequence Number 2
Notes
Date Text
2004-07-06 00:00:00************* UNSAT *****************8
  
 1)NOTE: PLEASE SEE A NEW TITLE BLOCK
 HAS BEEN ADDED FOR "HILLERS ENGINEERING"
 PLEASE PROVIDE ALL LICENSE #'S AS
 REQUIRED UNDER FAC 61G15-23.002. FS 471.
 023. PLEASE ALSO SEE "LEGAL SIGNATURE"
 MUST BE SIGNED. PLEASE VERIFY IF INITIAL
 AS SIGNED IS LEGAL SIGNATURE.
 PLEASE PROVIDE A SIGNED,DATED AND SEALED
 NOTORIZED LETTER FOR SIGNATURE.
  
 2)NOTE: PLEASE SHOW GROUNDING AT DETACH-
 -ED BLDG PER 250.32. PLEASE ALSO SEE
 250.50 FOR GROUNDING ELECTRODE SYSTEM TO
 BE SHOWN TO CWP, FOOTER STEEL.
  
 3)NOTE: PLEASE SEE A/C SYSTEM FOR GARAGE
 WHICH IS NOW SHOWN ON PANEL SCHEDULE.
 SHOWS CU AS 2-POLE AND AHU AS 1-POLE?
 THIS SYSTEM IS NOT SHOWN IN ANY LOAD
 CALCS.
  
 4)NOTE: PANEL "A" IS NOT SHOWN ON MDP.
 OCP? 200A?
  
 NOTES 1,2,3 PREVIOUS NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  