| Plan Review Notes For Permit 04021243 |
| Permit Number |
04021243 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-06 00:00:00 | ************* UNSAT *****************8 | | | | | | 1)NOTE: PLEASE SEE A NEW TITLE BLOCK | | | HAS BEEN ADDED FOR "HILLERS ENGINEERING" | | | PLEASE PROVIDE ALL LICENSE #'S AS | | | REQUIRED UNDER FAC 61G15-23.002. FS 471. | | | 023. PLEASE ALSO SEE "LEGAL SIGNATURE" | | | MUST BE SIGNED. PLEASE VERIFY IF INITIAL | | | AS SIGNED IS LEGAL SIGNATURE. | | | PLEASE PROVIDE A SIGNED,DATED AND SEALED | | | NOTORIZED LETTER FOR SIGNATURE. | | | | | | 2)NOTE: PLEASE SHOW GROUNDING AT DETACH- | | | -ED BLDG PER 250.32. PLEASE ALSO SEE | | | 250.50 FOR GROUNDING ELECTRODE SYSTEM TO | | | BE SHOWN TO CWP, FOOTER STEEL. | | | | | | 3)NOTE: PLEASE SEE A/C SYSTEM FOR GARAGE | | | WHICH IS NOW SHOWN ON PANEL SCHEDULE. | | | SHOWS CU AS 2-POLE AND AHU AS 1-POLE? | | | THIS SYSTEM IS NOT SHOWN IN ANY LOAD | | | CALCS. | | | | | | 4)NOTE: PANEL "A" IS NOT SHOWN ON MDP. | | | OCP? 200A? | | | | | | NOTES 1,2,3 PREVIOUS NOTES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|