| Date |
Text |
| 2004-07-20 00:00:00 | DENIED |
| | |
| | 1) THE TWO HOUR FIRE RATED WALLS ARE |
| | NOT REQUIRED FOR TYPE VI CONSTRUCTION. |
| | PLEASE REMOVE THE NOTE ON SHEET A1 |
| | SPECIFYING A 2 HOUR RATED WALL WITHIN |
| | 20 FEET OF THE PROPERTY LINE. |
| | |
| | 2) REVISE THE ATTIC ACCESS NOTE ON SHEET |
| | A4 FROM 97 FBC TO 2001 FBC. |
| | |
| | 3) ON SHEET A8 A SIMPSON SUR/L 210 IS |
| | SPECIFIED ATTACHED TO MASONRY WALL. THE |
| | PROPER CONNECTOR FOR ATTACHING TO |
| | MASONRY WITH TITEN SCREWS IS THE SIMPSON |
| | HUSUL/R 26-2. |
| | |
| | 4) THE BUILDING SECTION ON A9 SPECIFIES |
| | LATH AND STUCCO OVER PLYWOOD AND WOOD |
| | FRAME AT THE SECOND FLOOR. THE PLANS |
| | SHOW THE SECOND FLOOR IS MASONRY. THE |
| | H3 CONNECTOR SPECIFIED SHOULD BE A |
| | HETAL 16. PLEASE CORRECT. |
| | |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | PLEASE ATTACH COVER SHEETS FROM THE FL |
| | PRODUCT APPROVAL WEB SITE WITH THE STATE |
| | FL #. IF THE PRODUCT DOES NOT HAVE STATE |
| | PRODUCT APPROVAL, SUBMIT APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL. |
| | |
| | 6) SUBMIT ENERGY CALCULATION FORMS FOR |
| | EACH OF THE TWO CONDITIONED BUILDINGS ON |
| | THE PERMIT. SEE FBC 13-101.2.5.1 AND |
| | 101.2.5.2. THE PLAYROOM IN THE DETACHED |
| | GARAGE MUST USE SUB-CHAPTER 4 TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 7) THERE IS NO WINDOW AND DOOR SCHEDULE |
| | FOR THE DETACHED GARAGE AND THE ID |
| | MARKS DO NOT CORRESPOND WITH THE |
| | SCHEDULE ON A3. PLEASE CORRECT. |
| | |
| | IF YOU HAVE QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |