Plan Review Notes
Plan Review Notes For Permit 04021243
Permit Number 04021243
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-26 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 FAC 61G1-16.004, FS 471.023 AND FS 481.
 219. PLANS ARE REQ'D TO HAVE ALL INFOR-
 -MATION ON TITLE BLOCKS AS REQ'D PER
 ABOVE. PLANS ARE REQ'D TO HAVE TITLE BLK
 PLEASE ALSO SEE MISSING REQ'D LICENSE
 #'(S).
 PLEASE SEE THIS COMMENT STANDS FOR ALL
 PLANS AND FOR ALL TRADES WEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER.
  
 2)NOTE: PLEASE GARAGE NEEDS MORE INFOR-
 -MATION FOR THE FOLLOWING.
 MEANS OF DISC TO BE INDICATED,PER 225.31
 GROUNDING ELECTRODE PER 250.32
 LTS PER 210.70. NONE SHOWN FOR FRIST
 AND SECOND FLR?
 PLEASE ALSO SEE SWITCH IN MAIN HOUSE
 MENTIONS TO SW LT IN GARAGE? THIS MAY
 NOT BE PERMITTED UNLESS MEETING 225.31
 250.32,230.72 ETC.
 A/C UNTI NOT SHOWN ON ROOF W/ REQ'D
 GFI RECEPT PER 210.63,DISC PER 440.11.
 SD'S WILL BE REQ'D ON FIRST AND SECOND
 FLR. PER NFPA-72 8-1.4.2
  
 3)NOTE: PLEASE SEE 210.52C 1-5 FOR SPAC-
 -ING OF KITCHEN COUNTERSPACE RECEPTS.
 PLEASE SHOW ALL MIN REQ'D, INCLUDING
 PENINSULAR.
  
 4)NOTE: PLEASE SEE 210.8A6 FOR ALL RECEP
 -TS SERVING COUNTERSPACE TO BE GFI/GFI
 PROTECTED.
  
 5)NOTE: PLEASE SEE AHU'S ARE MISSING
 FROM PANEL SCHEDULE. PLEASE PROVIDE KW
 RATING FOR EACH UNIT. LOAD CALCS SHOW
 10KW TOTAL LOAD FOR BOTH?
 PLEASE CORRELATE WITH MECH PLANS. SHOW
 TWO 10KW UNITS. PLEASE ADJUST LOAD CALCS
 TO REFLECT LOADS.
  
 6)NOTE: PLEASE SEE LOAD SHOWN FOR MICRO-
 -WAVE ON LOADS CALCS. SHOWS 7.5KW FOR
 MICRO?
  
 7)NOTE: PLEASE SEE GARAGE A/C UNIT NOT
 LISTED ON GARAGE PANEL?
 PLEASE ALSO VERIFY IN LOAD CALCS.
  
 8)NOTE: PLEASE SEE NOTES BELOW RISER
 DIAGRAM. MENTIONS "ONE AMP BRANCH CIR-
 -CUIT" PLEASE ADJUST, MISPRINT?
  
 9)NOTE: PLEASE PROVIDE ROOM DESINATIONS
 ON PLANS.
  
 10)NOTE: PLEASE SEE RISER, SHOWS TWO
 PANEL "A"S.
  
 11)NOTE: PLEASE SHOW LT ETC REQ'D FOR
 AHU SHOWN TO BE IN ATTIC. 210.70
  
 12)NOTE: PLEASE CLARIFY, PLANS SHOW
 ELECTRIC WATER HEATER, YET LOAD CALCS
 INDICATE GAS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]