| 2004-04-26 00:00:00 | ************ UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | FAC 61G1-16.004, FS 471.023 AND FS 481. |
| | 219. PLANS ARE REQ'D TO HAVE ALL INFOR- |
| | -MATION ON TITLE BLOCKS AS REQ'D PER |
| | ABOVE. PLANS ARE REQ'D TO HAVE TITLE BLK |
| | PLEASE ALSO SEE MISSING REQ'D LICENSE |
| | #'(S). |
| | PLEASE SEE THIS COMMENT STANDS FOR ALL |
| | PLANS AND FOR ALL TRADES WEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER. |
| | |
| | 2)NOTE: PLEASE GARAGE NEEDS MORE INFOR- |
| | -MATION FOR THE FOLLOWING. |
| | MEANS OF DISC TO BE INDICATED,PER 225.31 |
| | GROUNDING ELECTRODE PER 250.32 |
| | LTS PER 210.70. NONE SHOWN FOR FRIST |
| | AND SECOND FLR? |
| | PLEASE ALSO SEE SWITCH IN MAIN HOUSE |
| | MENTIONS TO SW LT IN GARAGE? THIS MAY |
| | NOT BE PERMITTED UNLESS MEETING 225.31 |
| | 250.32,230.72 ETC. |
| | A/C UNTI NOT SHOWN ON ROOF W/ REQ'D |
| | GFI RECEPT PER 210.63,DISC PER 440.11. |
| | SD'S WILL BE REQ'D ON FIRST AND SECOND |
| | FLR. PER NFPA-72 8-1.4.2 |
| | |
| | 3)NOTE: PLEASE SEE 210.52C 1-5 FOR SPAC- |
| | -ING OF KITCHEN COUNTERSPACE RECEPTS. |
| | PLEASE SHOW ALL MIN REQ'D, INCLUDING |
| | PENINSULAR. |
| | |
| | 4)NOTE: PLEASE SEE 210.8A6 FOR ALL RECEP |
| | -TS SERVING COUNTERSPACE TO BE GFI/GFI |
| | PROTECTED. |
| | |
| | 5)NOTE: PLEASE SEE AHU'S ARE MISSING |
| | FROM PANEL SCHEDULE. PLEASE PROVIDE KW |
| | RATING FOR EACH UNIT. LOAD CALCS SHOW |
| | 10KW TOTAL LOAD FOR BOTH? |
| | PLEASE CORRELATE WITH MECH PLANS. SHOW |
| | TWO 10KW UNITS. PLEASE ADJUST LOAD CALCS |
| | TO REFLECT LOADS. |
| | |
| | 6)NOTE: PLEASE SEE LOAD SHOWN FOR MICRO- |
| | -WAVE ON LOADS CALCS. SHOWS 7.5KW FOR |
| | MICRO? |
| | |
| | 7)NOTE: PLEASE SEE GARAGE A/C UNIT NOT |
| | LISTED ON GARAGE PANEL? |
| | PLEASE ALSO VERIFY IN LOAD CALCS. |
| | |
| | 8)NOTE: PLEASE SEE NOTES BELOW RISER |
| | DIAGRAM. MENTIONS "ONE AMP BRANCH CIR- |
| | -CUIT" PLEASE ADJUST, MISPRINT? |
| | |
| | 9)NOTE: PLEASE PROVIDE ROOM DESINATIONS |
| | ON PLANS. |
| | |
| | 10)NOTE: PLEASE SEE RISER, SHOWS TWO |
| | PANEL "A"S. |
| | |
| | 11)NOTE: PLEASE SHOW LT ETC REQ'D FOR |
| | AHU SHOWN TO BE IN ATTIC. 210.70 |
| | |
| | 12)NOTE: PLEASE CLARIFY, PLANS SHOW |
| | ELECTRIC WATER HEATER, YET LOAD CALCS |
| | INDICATE GAS? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |