Plan Review Notes
Plan Review Notes For Permit 04021243
Permit Number 04021243
Review Stop B
Sequence Number 1
Notes
Date Text
2004-05-17 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FIRM LICENSE NUMBER IS MISSING FROM
 THE TITLE BLOCK. SEE FAC 61G1-16.04.
  
 3) REVISE CONSTRUCTION TYPE ON SHEET A1
 TO TYPE VI UNPROTECTED. FBC TABLE 600
 REQUIRES EXTERIOR BEARING WALLS WITHIN
 20 FEET OF THE PROPERTY LINE TO HAVE A
 2 HOUR FIRE RATING.
  
 4) PROVIDE A CLEAR SECTION DETAIL OF THE
 PARAPET WALLS.
  
 5) SPECIFY ON THE PLAN THAT THE WWM IN
 THE SLAB WILL BE SUPPORTED AT 3'OC AS
 REQUIRED BY FBC 1909.3.
  
 6)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 SPECIFY THE ABOVE INFORMATION FOR THE
 RESIDENCE AND THE DETACHED GARAGE.
  
 7) SPECIFY THE BOTTOM CORD LIVE LOAD FOR
 THE ATTIC SPACE. SEE FBC TABLE 1604.1.
  
 8) THERE IS A DISCREPANCY IN THE
 DIMENSIONS AT THE REAR OF THE STRUCTURE
 BETWEEN THE FOUNDATION PLAN AND THE
 FIRST FLOOR PLAN. PLEASE CORRECT.
  
 9) IN THE FIREBLOCKING NOTE ON A3 CHANGE
 THE CODE REFERENCED FROM SBC TO 2001 FBC
 REVISE SCHEDULE NOTE 5 TO 2001 FBC.
  
 10) ON SHEET A4 REVISE HANDRAIL NOTES
 AND ATTIC ACCESS NOTE TO FBC.
  
 11) SCUPPERS, OVERFLOW SCUPPERS AND
 LEADERS SHALL BE SIZED AND DISCHARGED IN
 ACCORDANCE WITH THE 2001 FBC PLUMBING
 PER FBC 1503.4.4 AND 1503.4.2. SPECIFY
 SIZES ON THE PLAN.
  
 12) ON SHEET A5 THE LEFT SIDE ELEVATION
 IS LESS THAN 10 FEET FROM THE PROPERTY
 LINE, FBC TABLE 600 ALLOWS 20% OF THE
 WALL AREA AS OPENINGS. PLEASE CORRECT
 THE CALCULATIONS.
  
 13)NOTE 6 ON A3 SPECIFIES IMPACT RESIST-
 ANT GLAZING AND THE NOTE ON A5 REFERS TO
 HURRICANE PANELS. PLEASE CLARIFY.
  
 14) REVISE THE DRAFTSTOP NOTE ON A7 TO
 REFERENCE THE FBC.
  
 15) CORRECT THE TYPO IN THE BEAM
 SCHEDULE ON A7 TO B10 FROM B0.
  
 16) REVISE THE SEMCO STRAPS SPECIFIED ON
 A7 TO A CURRENT STRAP WITH STATE PRODUCT
 APPROVAL.
  
 17)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23. REVISE THE UPLIFT VALUE OF
 THE SIMPSON HETAL 20 TO 1810#, WHICH IS
 THE VALUE GIVEN IN THE CURRENT CATALOG
 THAT DOESN'T INCLUDE A ONE THIRD
 INCREASE IN THE STEEL CALCULATIONS.
  
 18) UPDATE THE NOTES ON A9 TO REFERENCE
 THE 2001 FLORIDA BUILDING CODE.
  
 19) REVISE THE ROOF NOTES ON DETAILS 2
 AND 3 ON A12 TO REFERENCE 2001 FBC.
  
 20) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE 3/16" DIA. TAP CONS IN DETAIL 10 ON
 A12.
  
 21) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE 5/8" DIA. EXPANSION ANCHORS AT THE
 2X8 LEDGER IN DETAIL 3 ON A12.
  
 22) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE EXPANSION ANCHORS FOR LEDGERS.
  
 23) THE ID TAG AT THE GARAGE DOOR ON THE
 FLOOR PLAN ON A14 IS INCORRECT. IT
 SHOULD READ 1 ON A13.
  
 24) THE TWO FRONT WINDOWS ON THE SECOND
 FLOOR PLAN ON A14 DO NOT HAVE ID TAGS.
  
 25) SPECIFY ON THE PLANS IF DETACHED
 GARAGE IS TO HAVE IMPACT RESISTANT
 WINDOWS OR STORM PANELS.
  
 26) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 STATE OR LOCAL PRODUCT APPROVAL
 INFORMATION IN ADDITION TO PRODUCT NOAS.
  
 27) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR THE FOLLOWING ITEMS SHOWN ON PLANS:
 - ARCHED TOP INSWING ENTRY DOOR
 - ARCHED TOP WINDOW
  
 28) SUBMIT ENERGY CALCULATIONS FOR THE
 HOUSE WITH 2592 SQFT OF CONDITIONED
 SPACE AND DETACHED GARAGE WITH 372 SQFT
 OF CONDITIONED SPACE. EACH STRUCTURE IS
 REQUIRED TO HAVE A FORM AND CALCS.
  
 29) SPECIFY ON THE PLANS THE INSULATION
 FOR THE WALLS, FLOORS AND CEILING OF THE
 PLAYROOM IN THE DETACHED GARAGE.
  
 30) THE TWO STORY WALL SECTION 3 ON A12
 SPECS. R19 BATT INSULATION AND THE
 ENERGY CALCS. SPECIFY R30 INSULATION.
 PLEASE CORRECT.
  
 31) SEE ADDITIONAL NOTES ON THE REVIEWED
 PLANS.
  
 32)PLEASE RETURN ONE SET OF OLD DRAWINGS
 WITH NEW PLANS IN ORDER TO EXPEDIATE
 PLAN REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714