Plan Review Notes
Plan Review Notes For Permit 04021186
Permit Number 04021186
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-05 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQ'D UNDER FS 481.219
 AND FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 PANEL MAY NOT BE LOCATED ON EXIT/EGRESS
 STAIRWELL.
  
 3)NOTE: PLANS DO NOT INCLUDE "SECOND"
 FLOOR FOR REVIEW.
 PLANS NOT COMPLETE FOR SUFFICENT REVIEW
  
 4)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS.
  
 5)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT/REAR RECEPTS.
  
 6)NOTE: PLEASE SEE NO INFORMATION SUBMIT
 -TED FOR HOUSE PANEL FOR LAUNDRY EQUIP-
 -MENT.
 NO COMMON BRANCH CIRCUITS FROM APT
 PANELS PERMITTED IN COMMON AREA.
  
 7)NOTE: PLEASE SEE MISSING EGRESS LIGHT-
 ING PER LS 101 5-8 , 210.70 NEC
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 9) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10)NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
 EQUIPMENT GROUND IS SHOWN ON LINE SIDE
 OF METER>250.6
  
 11)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 12)NOTE: PLEASE SEE 210.11C1, 220.16 FOR
 MIN SMALL APPL.
  
 13)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCS FOR ALL ELECTRICAL SHOWN.
 NEED MORE INFORMATION.
  
 14)NOTE: PLEASE SHOW LOCATION OF SERVICE
 AND MAINS. MAINS TO BE GROUPED PER
 230.72.
 RISER SHOWS A MAIN DISC AND MCB PANEL??
 IF MCB IS SHOWN, THEN IT WILL BE REQ'D
 TO BE INSTALLED.
  
 FYI, NO LOW VOLTAGE SHOWN FOR PHONE/TV
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]