Plan Review Notes
Plan Review Notes For Permit 04021184
Permit Number 04021184
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-01 00:00:00PROVISO:
 1.PLAN INDICATES A WINDOW (3' X 3'),
 PER 2001FBC(M) 402.3.1 WINDOWS SHALL
 HAVE NO LESS THAN 3 SQ FT OF OPEN SPACE
 OTHERWISE MECHANICAL VENTILATION WILL
 BE REQUIRED.
  
 2.FAN SHUTDOWN WITH NOTIFICATION TO
 ALARM/STROBE ON SYSTEMS WITH A DESIGN
 CAPACITY GREATER THAN 2,000 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.