| Plan Review Notes For Permit 04021150 |
| Permit Number |
04021150 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-01 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE COMPUTE LOAD CALCULATIONS PER | | | 220.3. NOTE THAT DEMAND FACTORS THAT | | | WERE TAKEN ARE FOR DWELLING UNITS. SEE | | | 210.19 FOR CONTINUOUS LOADS'INCLUDING | | | 220.3(B)(9)' SHOW THAT CALCULATION AS | | | WELL. | | | | | | 2} REGARDING THE AIR HANDLERS PLEASE SEE | | | 220.3(B)(1), @ 100%. THERE IS NO DEMAND | | | FACTOR FOR COMMERCIAL A/C. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW | | | NOTES. PLEASE CORRELATE PLANS/PAPERWORK | | | FOR COTTAGES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|