Plan Review Notes
Plan Review Notes For Permit 04021148
Permit Number 04021148
Review Stop P
Sequence Number 2
Notes
Date Text
2004-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) CALCULATIONS FOR UPPER ROOF DO NOT
 SHOW 1/2 AREA OF VERITCAL WALLS AS REQ-
 QUESTED. THE ROOF AREA AS SCALED OUT IS
 THE SAME AS INDICATED ON CALCULATIONS
 WITH VERTICAL WALLS, (PARAPETS), ADDED.
 SHOW DIMENSIONS OF ROOF AREA AND SHOW
 HEIGHT OF PARAPETS TO CONFIRM CALCULAT-
 IONS.
 2) SUBMIT THE SAME INFORMATION FOR LOW-
 ER ROOF. SUBMIT A DETAIL FOR LOWER ROOF
 SHOWING GUTTER AND DOWNSPOUT INDICATED
 IN CALCULATIONS ON SHT A4. 5" GUTTER IS
 NOT SUFFICIENT FOR THE ROOF AREA TO BE
 DRAINED PER TABLE 1106.6. SHOW SLOPE OF
 GUTTER AND SHOW HIGH POINT OF GUTTER AND
 LOCATION OF DOWNSPOUT. INDICATE SLOPE OF
 GUTTER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]