| Plan Review Notes For Permit 04021148 |
| Permit Number |
04021148 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-05-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1) CALCULATIONS FOR UPPER ROOF DO NOT | | | SHOW 1/2 AREA OF VERITCAL WALLS AS REQ- | | | QUESTED. THE ROOF AREA AS SCALED OUT IS | | | THE SAME AS INDICATED ON CALCULATIONS | | | WITH VERTICAL WALLS, (PARAPETS), ADDED. | | | SHOW DIMENSIONS OF ROOF AREA AND SHOW | | | HEIGHT OF PARAPETS TO CONFIRM CALCULAT- | | | IONS. | | | 2) SUBMIT THE SAME INFORMATION FOR LOW- | | | ER ROOF. SUBMIT A DETAIL FOR LOWER ROOF | | | SHOWING GUTTER AND DOWNSPOUT INDICATED | | | IN CALCULATIONS ON SHT A4. 5" GUTTER IS | | | NOT SUFFICIENT FOR THE ROOF AREA TO BE | | | DRAINED PER TABLE 1106.6. SHOW SLOPE OF | | | GUTTER AND SHOW HIGH POINT OF GUTTER AND | | | LOCATION OF DOWNSPOUT. INDICATE SLOPE OF | | | GUTTER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|