| Plan Review Notes For Permit 04021148 |
| Permit Number |
04021148 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2001 CHAPTER 1 | | | | | | 1) ROUTE PLANS TO THE DEPT. OF BUSINESS | | | REGULATION HOTEL AND RESTAURANT DIVISION | | | FOR REVIEW. 201 W BROWARD BLVD. SUITE | | | 104 FT. LAUDERDALE FLA. (954) 958-5520 | | | SECTION 104.1.7 | | | 2) SHT A1A IF BEVERAGE BAR HAS WATER | | | SUPPLY, A WATER RISER DIAGRAM SHALL BE | | | REQUIRED PER SECTION 104.3.1.1 | | | 3) SHT A4 ROOF PLAN, SUBMIT CALCULATIONS | | | FOR UPPER ROOF PRIMARY AND SECONDARY | | | ROOF DRAINS PER SECTIONS 1106 & 1107 | | | AND ALL SUBSECTIONS. SHOW SQUARE FEET OF | | | ROOF & 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS. | | | 4) SHT A4 ROOF PLAN, SUBMIT CALCULATIONS | | | FOR LOWER ROOF. SHOW LOCATION AND SIZE | | | OF PRIMARY AND SECONDARY ROOF DRAINS. | | | SHOW SQUARE FEET OF LOWER ROOF AND SHOW | | | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING | | | PARAPETS. SHOW SQUARE FEET OF UPPER ROOF | | | BEING ADDED TO LOWER ROOF. SHOW SIZE OF | | | ALL RWL PIPING AND OR DOWNSPOUTS FOR | | | EXISTING ROOF. IF LOWER ROOF IS SLOPED, | | | INDICATE SLOPE ON PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|