Plan Review Notes
Plan Review Notes For Permit 04021148
Permit Number 04021148
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-24 00:00:00DENIED:
 1.PROVIDE ADDITIONAL INFORMATION ON
 THE CONDENSATE.PER CITY CODE SEC.
 90-125 (5), CONDENSATE SHALL TERMINATE
 INTO THE STORM DRAIN.PER 2001 FBC(M)
 307.2.1. #1, UNITS LARGER THAN 6 TON,
 CONDENSATE SHALL TERMINATE INTO STORM
 DRAIN OR AN APPROVED DRY WELL.
  
 2.PLEASE PROVIDE ENERGY CALCULATIONS
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 400.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.