| 2004-03-24 00:00:00 | DENIED: | | | 1.PROVIDE ADDITIONAL INFORMATION ON | | | THE CONDENSATE.PER CITY CODE SEC. | | | 90-125 (5), CONDENSATE SHALL TERMINATE | | | INTO THE STORM DRAIN.PER 2001 FBC(M) | | | 307.2.1. #1, UNITS LARGER THAN 6 TON, | | | CONDENSATE SHALL TERMINATE INTO STORM | | | DRAIN OR AN APPROVED DRY WELL. | | | | | | 2.PLEASE PROVIDE ENERGY CALCULATIONS | | | PER 2001 FBC CHAPTER 13 SUB-CHAPTER 400. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|