| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED, |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 2} THE DOWNSTAIR BEDROOM LABLED #3 (SAME |
| | AS UPSTAIR #3) NEEDS AN ADDED |
| | RECEPTACLE PER 210.52(A)(1). |
| | |
| | 3} THE DISCONNECTS AT THE A/C UNITS DO |
| | NOT COMPLY WITH 110.26 CLEARANCE |
| | REQUIREMENTS. PLEASE INDICATE, ON THE |
| | DRAWING, PLACEMENT FOR COMPLIANCE. |
| | |
| | 4} PLEASE SEE THE MECHANICAL PLANS TO |
| | INSURE PLACEMENT OF THE SMOKE DETECTORS |
| | IS IN COMPLIANCE WITH THE CLEARANCE |
| | REQUIREMENTS OF NFPA-72, 1999 ED., CH |
| | #8. |
| | |
| | 5} NOTE #15 REFERENCES THE 1997 SBC. |
| | THIS PLAN IS BEING REVIEWED UNDER THE |
| | 2001 FLORIDA BUILDING CODE. ALSO IT |
| | SHOULD BE NOTED THAT SMOKE DETECTORS IN |
| | BEDROOMS MUST COMPLY WITH 210.12 AND BE |
| | ARC FAULT PROTECTED. |
| | |
| | 6} PLEASE INDICATE THE AMPERAGE RATING |
| | OF THE FUSE OR BREAKER IN THE MAIN |
| | DISCONNECT, ALSO THE AIC RATING OF SAME. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |