| Notes |
| Date |
Text |
| 2004-04-06 00:00:00 | DENIED | | | 1.PRODUCT APPROVAL FOR ENTRY DOOR | | | MISSING.SUBMIT 2 COPIES. | | | APPICATIONS FOR LOCAL AND OR STATE | | | SITE SPECIFIC PRODUCT APPROVAL NOT | | | REQUIRED IF THE PRODUCT IS LISTED ON | | | THEFBC PRODUCT APPROVAL SITE.ALL | | | PRODUCT APPROVALS SUBMITTED ARE ON THE | | | FBC SITE.PLEASE REMOVE APPLICATIONS. | | | | | | 2.VALUATION OF $166,800 IS TO LOW | | | BASED UPON SBCCI BUILDING VALUATION | | | DATA.BUILDING VALUE HAS BEEN CHANGED | | | TO $233,750.ADDITIONAL PERMIT FEES | | | OF $676.20 AREW DUE BEFORE A PERMIT MAY | | | BE ISSUED. | | | | | | 3.WINDOW BUCKS SHALL COMPLY WITH | | | FBC 1707.4.4.2 BUCKS SHALL EXTEND | | | BEYOND THE INTERIOR FACE OF THE WINDOW | | | OR DOOR FRAME SUCH THAT FULL SUPPORT OF | | | THE FRAME IS PROVIDED. | | | SHOW ON DETAIL. | | | | | | 4.BALISTERS ON GUARD RAILS AND STAIR | | | RAILINGS SHALL BE SPACED THAT A 4" | | | DIAMETER SHERE CANNOT PASS THROUGH. | | | FBC 1015.3SHOW ON DETAIL. | | | | | | 5.SUBMIT A SECOND COPY OF ENERGY CALCS | | | | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|