Plan Review Notes
Plan Review Notes For Permit 04021116
Permit Number 04021116
Review Stop B
Sequence Number 2
Notes
Date Text
2004-04-14 00:00:00DENIED
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PRODUCT APPROVALS FOR WINDOWS NOT
 SUBMITTED.SUBMIT 2 COPIES.IMPACT
 PROTECTION NEEDED IF IMPACT GLASS IS NOT
 PROVIDED.SEPERATE WOULD BE REQUIRED
 FOR IMPACT PROTECTION.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.ENERGY CALCS NOT SIGNED.
  
 4.WINDOW AND DOOR BUCKS SHALL COMPLY
 WITH FBC 1707.4.4.2 UNLESSS OTHERWISE
 TESTED BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE
 FRAME IS PROVIDED.SHOW DETAIL.
  
 5.NEW STUDIO ROOM TO COMPLY WITH
 WPB AMMENDMENT TO THE FBC 1804.1.7
 THE LOWEST BUILDING FLOOR ELEVATION
 IN A HABITABLE AREA SHALL BE A MINIMUM
 OF 4IN. ABOVE THE FINISHED GRADE.
 SHOW DETAIL ON PLANS.
  
 6. FEES STILL DUE ON REVISED BUILDING
 VALUATION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672