Plan Review Notes
Plan Review Notes For Permit 04021098
Permit Number 04021098
Review Stop E
Sequence Number 4
Notes
Date Text
2004-09-22 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE REVISED RISER DIAGRAM
 , MAINS ARE NOT GROUPED AS REQUIRED
 UNDER 230.72. SHOWS A MCB INSIDE AND
 A MAIN DISC OUTSIDE FOR THE OTHER.
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE TOTAL # OF RECESSED LTS.
  
 3)NOTE: LT REQUIRED IN DINING ROOM.
 210.70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  