Plan Review Notes
Plan Review Notes For Permit 04021098
Permit Number 04021098
Review Stop E
Sequence Number 3
Notes
Date Text
2004-05-04 00:00:00******* PLANS REDLINED ****
  
 1)NOTE: PLEASE SEE NOW SOME OF THE EXIST
 -ING LAYOUT IS SHOWN.
 PLEASE SEE ALL EXISTING ELECTRICAL MUST
 BE BROUGHT UP TO CODE.
 NO MEANS OF EGRESS LIGHTING OR CONTROL
 IS SHOWN FOR EXISTING STAIRWAY.210.70
 NO CONTROL FOR MEANS OF EGRESS TO OUT-
 -SIDE. 210.70
  
 2)NOTE: PLEASE SEE 210.52E FOR REQ'D
 OUTSIDE RECEPT.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE MISSING SD ON FIRST FLR
 LEADING TO THE FLR ABOVE.
  
 OWES 2ND RESUB FEE. SEE BZ ATTACHED.
 SOME NOTES WERE FROM FIRST REVIEW ALSO.
  
 ALL REVISIONS TO BE SUBMITTED BEFORE
 ROUGH.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]