| Plan Review Notes For Permit 04021098 |
| Permit Number |
04021098 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-04 00:00:00 | ******* PLANS REDLINED **** | | | | | | 1)NOTE: PLEASE SEE NOW SOME OF THE EXIST | | | -ING LAYOUT IS SHOWN. | | | PLEASE SEE ALL EXISTING ELECTRICAL MUST | | | BE BROUGHT UP TO CODE. | | | NO MEANS OF EGRESS LIGHTING OR CONTROL | | | IS SHOWN FOR EXISTING STAIRWAY.210.70 | | | NO CONTROL FOR MEANS OF EGRESS TO OUT- | | | -SIDE. 210.70 | | | | | | 2)NOTE: PLEASE SEE 210.52E FOR REQ'D | | | OUTSIDE RECEPT. | | | | | | 3)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | PLEASE SEE MISSING SD ON FIRST FLR | | | LEADING TO THE FLR ABOVE. | | | | | | OWES 2ND RESUB FEE. SEE BZ ATTACHED. | | | SOME NOTES WERE FROM FIRST REVIEW ALSO. | | | | | | ALL REVISIONS TO BE SUBMITTED BEFORE | | | ROUGH. | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|