| 2004-04-20 00:00:00 | ************* UNSAT ************ |
| | |
| | PLEASE SEE SOME NOTES FROM THE FIRST |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE 250.66 FOR SIZING |
| | OF GEC. MIN #2. |
| | |
| | 2)NOTE: PLEASE SEE SD NOTE, IT HAS NOW |
| | BEEN CHANGED TO REFLECTA AND NOTE AFCI |
| | PROTECTION FOR RECEPTS AND LTS. PLEASE |
| | SEE 210.12 OF THE 2002 NEC. AFCI IS |
| | REQ'D FOR ALL "OUTLETS". THIS WOULD |
| | INCLUDE SD'S. |
| | |
| | NEW COMMENTS. |
| | |
| | 3)NOTE: PLANS SHOW ONE PANEL BEING |
| | INSTALLED IN LAUNDRY RM AND THE OTHER |
| | IS NOT SHOWN? |
| | PLEASE SEE 230.72 FOR GROUPING OF MAINS, |
| | RISER SHOWS 2-150A MCB PANELS? |
| | THERE MAY NOT BE MORETHAN 8' OF UNPRO- |
| | -TECTED CONDUCTORS INSIDE THE BLDG. |
| | 230.70 LOCAL AMENDMENTS. IF SO, MAINS |
| | ARE REQ'D W/ OCP OUTSIDE. |
| | |
| | 4)NOTE: PLEASE SHOW A LAYOUT OF EXSITNG |
| | DWELLING RMS SHOWING EITHER EXISTING |
| | MEETING CODE COMPLIANCE OR NEW TO BE |
| | INSTALLED. PLEASE SEE FBC CHAPTER 34 |
| | 3401.7.1.1 PLEASE SEE THAT THE ENTIRE |
| | EXISITNG DWELLING WOULD NEED TO BE |
| | BROUGHT UP TO CODE FOR ELECTRICAL. |
| | PLEASE SEE OTHER REVIEWS. |
| | |
| | 5)NOTE: THIS IS ONLY A NOTE AND MUST BE |
| | GIVEN ON ANY REVIEWS WITH COMMENTS ON |
| | SECOND REVIEW WHERE ANY COMMENTS FROM |
| | FIRST REVIEW WERE NOT ADDRESSED. |
| | PLEASE SEE COPY OF ATTACHED SHEET FOR |
| | FS 553.80(2)(B). THIS IS ONLY A NOTE |
| | AND NOTICE MUST BE GIVEN AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |