| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE GROUNDING ELECTRODE CONDUCTOR IS |
| | INCORRECT PER 250.66, SHOULD BE A |
| | MINIMUM OF #2 CU. |
| | |
| | 2} THE SMALL APPLIANCE CALCULATION ON |
| | THE PANEL SCHEDULE IS NOT IN COMPLIANCE |
| | WITH 220.16(A), 1500 VA PER CIRCUIT. |
| | |
| | 3} THERE IS NO LAUNDRY CIRCUIT IN THE |
| | CALCULATION. SEE 220.16(B). |
| | |
| | 4} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE PER 210.11(C)(3). |
| | |
| | 5} THE NOTE REGARDING ARC FAULT |
| | PROTECTION SHOULD INCLUDE ALL OUTLETS |
| | IN THE BEDROOM, NOT JUST RECEPTACLES. |
| | SEE 210.12. |
| | |
| | 6} SERVICE RECEPTACLES ARE REQUIRED TO |
| | COMPLY WITH 210.63.(A/C UNITS). |
| | |
| | 7} A RECEPTACLE IS REQUIRED ON THE REAR |
| | OF THE ADDITION TO COMPLY WITH 210.52(E) |
| | |
| | 8} THE RECEPTACLE IN THE LAUNDRY AT THE |
| | SINK MUST BE GFI PROTECTED PER 210.8. |
| | |
| | 9} THE SMOKE DETECTOR IN THE KITCHEN |
| | MUST COMPLY WITH 8-1.4.2 NFPA-72. |
| | |
| | 10} THE OUTLET SUPPLYING THE WHIRLPOOL |
| | MUST COMPLY WITH 680.71.(GFI). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |