Plan Review Notes
Plan Review Notes For Permit 04021098
Permit Number 04021098
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR IS
 INCORRECT PER 250.66, SHOULD BE A
 MINIMUM OF #2 CU.
  
 2} THE SMALL APPLIANCE CALCULATION ON
 THE PANEL SCHEDULE IS NOT IN COMPLIANCE
 WITH 220.16(A), 1500 VA PER CIRCUIT.
  
 3} THERE IS NO LAUNDRY CIRCUIT IN THE
 CALCULATION. SEE 220.16(B).
  
 4} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11(C)(3).
  
 5} THE NOTE REGARDING ARC FAULT
 PROTECTION SHOULD INCLUDE ALL OUTLETS
 IN THE BEDROOM, NOT JUST RECEPTACLES.
 SEE 210.12.
  
 6} SERVICE RECEPTACLES ARE REQUIRED TO
 COMPLY WITH 210.63.(A/C UNITS).
  
 7} A RECEPTACLE IS REQUIRED ON THE REAR
 OF THE ADDITION TO COMPLY WITH 210.52(E)
  
 8} THE RECEPTACLE IN THE LAUNDRY AT THE
 SINK MUST BE GFI PROTECTED PER 210.8.
  
 9} THE SMOKE DETECTOR IN THE KITCHEN
 MUST COMPLY WITH 8-1.4.2 NFPA-72.
  
 10} THE OUTLET SUPPLYING THE WHIRLPOOL
 MUST COMPLY WITH 680.71.(GFI).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026