| 2004-03-17 00:00:00 | DENIED |
| | |
| | 1.IMPACT PROTECTION REQUIRED ON ALL |
| | OPENINGS. |
| | |
| | 2.PRODUCT APPROVALS FOR "CONSTRUCTION |
| | GLASS INDUSTRIES" NOT LISTED ON THE |
| | FBC PRODUCT APPROVAL SITE. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONPLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 3.2 COPIES OF ALL PRODUCT APPROVALS |
| | REQUIRED. |
| | |
| | 4.NO PRODUCT APPROVALS SUBMITTED FOR |
| | SINGE EXTERIOR DOORS. |
| | |
| | 5.VERIFY FINISH FLOOR ELEVATION OF |
| | UTILITY ROOM IS A MINIMUM 4" ABOVE |
| | FINISH GRADE WPB AMMENDMENTS 1804.17 |
| | |
| | 6. SECTION 5/A7 USP-AD52 ANCHOR IS NOT |
| | AVALID USP ANCHOR. |
| | |
| | 7.WINDOW #9 SHALL COMPLY WITH SECTION |
| | FBC 2405.2.1 SAFTEY GLAZING. |
| | |
| | 8.SHOW ATTIC ACCESS COMPLYING WITH |
| | FBC 2309.6 20 X 36" OPENING |
| | |
| | 9.FIRST AND SECOND FLOOR SLEEPING ROOM |
| | EGRESS WINDOWS SHALL COMPLY WITH |
| | FBC 1005.4SUBMIT A WINDOW SHEDULE |
| | FOR SECOND FLOOR SHOWING SLEEPING ROOMS. |
| | |
| | 10.PROJECT VALUATION TOO LOW. BASED |
| | UPON SBCCI BUILDING VALUATION DATA |
| | THE ROOM ADDITION ALONE WILL BE |
| | $143,992 PLUS THE ADDITION WORK ON THE |
| | EXISTING BUILDING.SUBMIT AN ACCURATE |
| | REVISED PROJECT VALUE. |
| | |
| | PLEASE ADDRESS THE ABOVE COMMENTS |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |