| 2004-03-05 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 2) SUITABLE ROADS ARE TO BE PROVIDED | | | DURING CONSTRUCTION FOR FIRE AND | | | PARAMEDICAL EQUIPMENT. | | | | | | 3) ELECTRONIC SWITCHES, CHAINS AND LOCKS | | | ARE REQUIRED ON THE FIRELINE BACKFLOW | | | DEVICES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|