Notes
Date Text
2004-03-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SHTS A-6, A-8 & A-18. A-6 SHOW OVER-
 FLOW SCUPPERS 12"X20" (TYP), A-8 SHOWS
 OVERFLOW SCUPPERS 12"X12" (TYP), AND
 SHT A-18 DETAIL 3/18 SHOWS OVERFLOW
 SCUPPERS 12"X20". PLEASE CLAIRFY. -
 WILL THE SCUPPERS ON THE LOWER ROOFS BE
 SIZED AS TYPICAL?
 2) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 INITIALS ARE NOT ACCEPTABLE PER A RULING
 BY THE FBPE. A COPY OF THE PLUMBING
 SHEET WILL BE PLACED ON FILE FOR REVIEW
 BY FBPE.
  