Plan Review Notes
Plan Review Notes For Permit 04021075
Permit Number 04021075
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-02-27 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESS REQUIRED. SIX HIGH
 NUMBERS REQUIRED.
  
 3) KNOX-BOX REQUIRED.
  
 4) ELECTRONIC SWITCHES REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 5) FDC'S SHALL BE WITHIN 150 FEET OF
 A FIRE HYDRANT.
  
 6) SUITABLE ROADS ARE REQUIRED FOR
 FIRE AND PARAMEDICAL EQUIPMENT.
  
 7) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 8) NEW FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 9) NOTES # 17 AND 19 ARE INCORRECT.
 PLEASE REVISE PLANS AS NECESSARY.
  
 10) FIRE PUMP ROOM REQUIRED EMERGENCY
 LIGHTING.
  
 11) PLEASE EXPLAIN EXITING RATIONALE
 DIRECTLY BEHIND DUMPSTER ENCLOSURE.
  
 12) PLEASE EXPLAIN SECURITY BAR NOTE
 # 3 ON PAGE M2.2.
  
 13) EXTERIOR STAIRS SHALL BE SLIP
 RESISTANT.
  
 14) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ALL TENANT IMPROVEMENT PLANS.
  
 15) PLEASE EXPLAIN PUMP ROOM AND
 STORAGE ROOM DOORS THAT OPEN ONTO
 EXIT DISCHARGE. ALSO HANDRAILS ARE
 REQUIRED ON BOT SIDES OF STAIRS.
  
 16) PLEASE PROVIDE CODE DATA BOX.
  
 17) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910