| 2004-02-27 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED |
| | PRIOR TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 2) BUILDING ADDRESS REQUIRED. SIX HIGH |
| | NUMBERS REQUIRED. |
| | |
| | 3) KNOX-BOX REQUIRED. |
| | |
| | 4) ELECTRONIC SWITCHES REQUIRED ON |
| | FIRE LINE BACKFLOW DEVICE. |
| | |
| | 5) FDC'S SHALL BE WITHIN 150 FEET OF |
| | A FIRE HYDRANT. |
| | |
| | 6) SUITABLE ROADS ARE REQUIRED FOR |
| | FIRE AND PARAMEDICAL EQUIPMENT. |
| | |
| | 7) NO FIRE SPRINKLER PLANS PROVIDED |
| | WITH DRAWINGS. |
| | |
| | 8) NEW FIRE ALARM SYSTEMS SHALL BE |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | 9) NOTES # 17 AND 19 ARE INCORRECT. |
| | PLEASE REVISE PLANS AS NECESSARY. |
| | |
| | 10) FIRE PUMP ROOM REQUIRED EMERGENCY |
| | LIGHTING. |
| | |
| | 11) PLEASE EXPLAIN EXITING RATIONALE |
| | DIRECTLY BEHIND DUMPSTER ENCLOSURE. |
| | |
| | 12) PLEASE EXPLAIN SECURITY BAR NOTE |
| | # 3 ON PAGE M2.2. |
| | |
| | 13) EXTERIOR STAIRS SHALL BE SLIP |
| | RESISTANT. |
| | |
| | 14) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR ALL TENANT IMPROVEMENT PLANS. |
| | |
| | 15) PLEASE EXPLAIN PUMP ROOM AND |
| | STORAGE ROOM DOORS THAT OPEN ONTO |
| | EXIT DISCHARGE. ALSO HANDRAILS ARE |
| | REQUIRED ON BOT SIDES OF STAIRS. |
| | |
| | 16) PLEASE PROVIDE CODE DATA BOX. |
| | |
| | 17) PLEASE INDICATE FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |