| Plan Review Notes For Permit 04021075 |
| Permit Number |
04021075 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-10 00:00:00 | *************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE FIRE REVIEW NOTES, | | | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. (PUMP RM EM LTS.) | | | | | | 2)NOTE: PLEASE SEE FEEDERS FROM MAIN TO | | | "1HP", SHOWS #3'S ON 200A OCP. PLEASE | | | SEE 310.16 FOR MIN SIZE OF CONDUCTORS. | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3,230.42 ETC. | | | | | | 4)NOTE: PLEASE SEE THAT IT DOES APPEAR | | | TO HAVE SERVICE EQUIPMENT FOR FIRE PUMP | | | SHOWN ON ELECTRICAL RM PLANS.? | | | RISER IS SHOWN BUT WHERE IS MAIN ETC? | | | PLEASE SEE 230.72,230.76,230.79 FOR | | | LOCATION OF DISC.MEANS. | | | PLEASE ALSO SEE CODE REFERENCED FOR | | | OCP OF FIRE PUMP. APPEARS TO BE A MIS- | | | -PRINT FOR CODE #. | | | PLEASE SUBMIT SPECS FOR FIRE PUMP FOR | | | FIRE REVIEW. | | | | | | 5)NOTE: PLEASE SHOW GROUNDING FOR TRANS- | | | -FORMER. 250.30 | | | | | | 6)NOTE: PLEASE SEE LOCAL AMENDMENT FOR | | | COLOR CODING OF 277/480V SYSTEMS. | | | BR/PURP/YELLOW. PLANS SHOW DIFF ORDER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|