Plan Review Notes
Plan Review Notes For Permit 04021075
Permit Number 04021075
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-10 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE SEE FIRE REVIEW NOTES,
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS. (PUMP RM EM LTS.)
  
 2)NOTE: PLEASE SEE FEEDERS FROM MAIN TO
 "1HP", SHOWS #3'S ON 200A OCP. PLEASE
 SEE 310.16 FOR MIN SIZE OF CONDUCTORS.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE THAT IT DOES APPEAR
 TO HAVE SERVICE EQUIPMENT FOR FIRE PUMP
 SHOWN ON ELECTRICAL RM PLANS.?
 RISER IS SHOWN BUT WHERE IS MAIN ETC?
 PLEASE SEE 230.72,230.76,230.79 FOR
 LOCATION OF DISC.MEANS.
 PLEASE ALSO SEE CODE REFERENCED FOR
 OCP OF FIRE PUMP. APPEARS TO BE A MIS-
 -PRINT FOR CODE #.
 PLEASE SUBMIT SPECS FOR FIRE PUMP FOR
 FIRE REVIEW.
  
 5)NOTE: PLEASE SHOW GROUNDING FOR TRANS-
 -FORMER. 250.30
  
 6)NOTE: PLEASE SEE LOCAL AMENDMENT FOR
 COLOR CODING OF 277/480V SYSTEMS.
 BR/PURP/YELLOW. PLANS SHOW DIFF ORDER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  