Plan Review Notes
Plan Review Notes For Permit 04021075
Permit Number 04021075
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-06 00:00:00****CORRECTIONS****
 ****PAID PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE CA NUMBER FROM FBPE IS TO BE
 ON EACH SHEET, FAC61G15-23.002.THE
 PRINTED NAME AND LICENSE NUMBER OF THE
 PERSON SEALING THE DOCUMENT IS TO BE ON
 EACH SHEET.
  
 2.)A SIGNATURE, NOT INITIALS, REQUIRED
 AS PER BUILDING OFFICIAL.
  
 3.)SEPARATE PERMIT REQUIRED FOR SIGNS.
  
 4.)SUBMIT THREE COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:
 4X4 SKYLIGHT
 STOREFRONT GLASS
 KNOCKOUT PANELS
 3X3 INTAKE LOUVER
 OVERHEAD DOOR
 WINDOWS
 DOORS
 LOUVERED DOORS
 IMPACT PROTECTION
 ANY OTHER ITEMS REQUIRED
  
 FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC REQUIRED IN ADDITION TO TEST
 REPORT.WWW.FLORIDABUILDING.ORG
  
 5.)PROVIDE A SURVEY FOR THIS
 PROPERTY.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND A RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 7.)IT IS DIFFICULT TO DETERMINE THE
 FLOOD ZONE FROM THE EXHIBIT PROVIDED.
  
 8.)PROVIDE AN ORIGINAL SEALED SOILS
 REPORT (COPIES WERE SUBMITTED).
  
 9.)RESIDENT INSPECTOR REQUIRED, CALL
 HAROLD PISKURA, 805-6711.
  
 10.) THREE SETS OF PLANS REQUIRED.
  
 11.) PROVIDE A FINISHED FLOOR ELEVATION
 ON THE FOUNDATION PLAN.
  
 12.) GUARDRAILS ARE TO COMPLY WITH
 FBC1608.2.2.
  
 13.) 4-A9 REFERS TO A10 FOR THE STAIR
 AND RAMP DETAIL, NOT ON THAT PAGE.
  
 14.) M01, THE RUSKIN LOUVER DETAIL IS
 ILLEGIBLE.
  
 15.) INDICATE WHERE THE HURRICANE
 SHUTTERS WILL BE STORED AND HOW THEY
 WILL BE STORED.IF THEY ARE NOT STORED
 HORIZONTALLY, PROVIDE A RACK DETAIL.
 PROVIDE A HURRICANE SHUTTER INSTALLATION
 SCHEDULE, SEE ATTACHED.
  
 16.) FBC13-101.1.6, SHELL BUILDING ARE
 TO COMPLY WITH METHOD B OF SUB-CHAPTER
 13-4.
  
 17.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 18.) PLEASE NOTE THAT THE ADDRESS ON
 THE PERMIT APPLICATION IS INCORRECT.
  
 19.) PROVIDE A LIFE SAFETY PLAN.SHOW
 COMPLIANCE WITH FBC CHAPTER 10.
  
 20.) PROVIDE A CODE ANALYSIS FOR THIS
 BUILDING (DECLARE A BUILDING TYPE,
 OCCUPANT LOAD, SPRINKLER AND PROTECTION
 INFORMATION, ETC.)
  
 21.) SHOW HOW YOU ARE COMPLYING WITH
 FBC CHAPTER 5.
  
 22.) PROVIDE A FIRE SPRINKLER PLAN,
 FBC104.3.1.1(5), FBC503.
  
 23.) PROVIDE A COPY OF THE UNITY OF
 TITLE.
  
 24.) WHEN RESUBMITTING, INCLUDE A
 TRANSMITTAL LETTER INCLUDING HOW EACH
 ITEM WAS ADDRESSED.