| Plan Review Notes For Permit 04021074 |
| Permit Number |
04021074 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-22 00:00:00 | PROVISO: | | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC 307.2.3 | | | | | | 2.PLAN INDICATES WALL MOUNT FOR THE | | | AHU.PER 2001 FBC(M) 603.1.3, A | | | MINIMUM OF 4" CLEARANCE AROUND THE AHU | | | IS REQUIRED FOR SEALING, INSPECTION, | | | CLEANING & MAINTENANCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|