| Permit Number |
04021074 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-04-06 00:00:00 | DENIED | | | 1.PRODUCT APPROVAL FOR ENTRY DOOR | | | MISSING.SUBMIT 2 COPIES. | | | APPLICATIONS FOR LOCAL AND OR STATE | | | SITE SPECIFIC PRODUCT APPROVAL NOT | | | REQUIRED IF PRODUCT IS LISTED ON THE | | | FBC PRODUCT APPROVAL SITE.ALL | | | PRODUCTSSUBMITTED ARE ON THE FBC SITE. | | | PLEASE REMOVE APPLICATIONS. | | | | | | 2.VALUATION OF $166,800 IS TO LOW | | | BASED UPON SBCCI BUILDING VALUATION | | | DATA. BUILDING VALUE HAS BEEN CHANGED | | | TO $233,750ADDITION PERMIT FEES OF | | | $676.20 ARE DUE BEFORE A PERMIT MAY BE | | | ISSUED. | | | | | | 3. WINDOW BUCKS SHALL COMPLY WITH | | | FBC 1707.4.4.2BUCKS SHALL EXTEND | | | BEYOND THE INTERIOR OR FACE OF THE | | | WINDOW OR DOOR FRAME SUCH THAT FULL | | | SUPPORT OF THE FRAME IS PROVIDED. | | | SHOW ON DETAIL. | | | | | | 4.BALISTERS ON GUARD RAILS AND STAIR | | | RAILINGS SHALL BE SPACED THAT A 4" | | | DIAMETER SPHERE CANNOT PAS THROUGH. | | | FBC 1015.3PLEASE REVISE DETAIL. | | | | | | 5.SUBMIT A SECOND COPY OF ENERY CALC'S | | | | | | | | | ANY QUESTIONS CONTACT ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|