2004-03-09 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5. SUBMIT SAME FOR REVIEW
 PRIOR TO CALLING ANY ELECTRICAL
 INSPECTIONS. ALSO PLEASE NOTE THESE MAY
 NOT BE REVIEWED IMMEDIATLY UPON
 SUBMITTING. ALLOW 2 TO 3 DAYS. SUBMIT
 THESE AS SOON AS POSSIBLE TO AVOID
 DELAYS WHEN INSPECTIONS ARE NEEDED.
 THIS INFORMATION MUST BE SUBMITTED BY
 THE DESIGN PROFESIONAL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026