| 2004-03-09 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. | | | PER 110.9/215.5. SUBMIT SAME FOR REVIEW | | | PRIOR TO CALLING ANY ELECTRICAL | | | INSPECTIONS. ALSO PLEASE NOTE THESE MAY | | | NOT BE REVIEWED IMMEDIATLY UPON | | | SUBMITTING. ALLOW 2 TO 3 DAYS. SUBMIT | | | THESE AS SOON AS POSSIBLE TO AVOID | | | DELAYS WHEN INSPECTIONS ARE NEEDED. | | | THIS INFORMATION MUST BE SUBMITTED BY | | | THE DESIGN PROFESIONAL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|